TM0066
Page 36 of 39
Issue 2.01
INTERNAL CONTROLS
SW1
4 Way DIL switch
Leaf 1 OFF
Sounder circuits constant
Leaf 1 ON
Sounder circuits pulsed
Leaf 2 ON
Zone 1 not latching mode
Leaf 3 ON
Initiates the test mode
Leaf 4 ON
Operates the processor fault counter
INTERNAL INDICATIONS
LED1
PS
Power supply fault
LED2
ALM
Alarm fault
LED3
DSP
Display disconnected
LED 4
-
Earth fault
ENGINEERS CONTROL
PROCRST
Processor reset
FCRST
Fault counter reset
EXTERNAL DIMENSIONS - 900(h) x 400(w) x 138(d) mm
WEIGHT - 22 kg (excluding batteries)
BATTERY CAPACITY
2 x 12V 6 Ah Yuasa sealed lead acid cells
Replacement period
4 years
CURRENT CONSUMPTION
Quiescent current
400 mA
Alarm current
600 mA (no sounder load)
Maximum power supply output is rated at 10.0 Amps.