the reset button check that the panel reverts to the operating condition, with the supply healthy
LED illuminated.
The audibility level of the sounders should be checked to ensure that they conform to BS 5839
Part 1, Section 2 clause 9.4.
NOTE Upon completion of commissioning of the system it is advisable to perform a
processor failure count check as described in the Engineers Controls section
of this manual. When a check has been performed, reset the counter to zero,
(8, 16 and 32 zone control panels only).