„Installation and operation manual for fireplace insert”
7
Note
•
Safe distance between the internal side of the chimney and combustible elements is at
least 16 cm in case of a brick chimney. In case of steel chimneys, the information is
specified by the manufacturer (X).
Insulated
steel chimney
Combustible
elements
X
Brick
chimney
160
Combustible
elements
Figure 5. Safe distance of the chimney from combustible elements (dimensions in mm).
•
Safe distance for conducting the connecting pipe (combustion gas pipe) through a
combustible wall is at least 20 cm.
Figure 6. Method of conducting the combustion gas pipe through a combustible wall
(dimensions in mm).
•
The smoke exhaust system must be unique to the insert.
200
200
200
Ściana palna
Rura spalinowa
Wypełnienie
(lekki beton lub wełna)
Kryza
z blachy stalowej
Filling (lightweight
concrete or wool)
Combustible wall
Combustion gas pipe
Steel sheet cap