Installation
2
Series N8700 User’s Guide
27
appropriate cut-outs for the larger sized wires as indicated in the
following figure. Secure the shield using the tab on the left side
and the M3 x 8mm flat head screw on the right side. Screw
tightening torque: 4.8 - 5.3 in-lb (0.54 – 0.6 Nm).
Load Connections for 150V, 300V and 600V Models
WARNING
SHOCK HAZARD
Hazardous voltages may exist at the outputs and the load
connections when using a power supply with a rated output greater than 40V.
To protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts. Ensure
that the load wiring insulation rating is greater than or equal to the maximum
output voltage of the power supply.
The 150V, 300V and 600V models have a four-terminal wire clamp
output connector. The two left terminals are the positive outputs and
the two right terminals are the negative outputs. The connector
specifications are as follows:
Wire Size:
AWG 18 to AWG 10
Stripping Length:
10 mm (0.4 in)
Torque:
4.4 – 5.3 in-lb (0.5 – 0.6 Nm)
Opening for wire sizes
from AWG 4-10.
Opening for wire sizes
from AWG 2-1/0.
(cut-out
has been removed)
Remove this cut-out for
wire sizes AWG 2/0- 3/0.
Remove this cut-out for
bus rail installation.