Keyscan Inc. – Technical Guide (PC109x - 04.15)
70
Bit Rate/Second
Jumper #
Jumper Settings
460,800
N/A
For future use – not supported on PC109x
Reset Jumper J1
The CIM has a reset jumper J1. If the board has been re-configured while powered, momentarily short J1 on
the CIM board to institute the changes.
Momentarily shorting the System Reset J6 jumper on the control board also effects changes to the CIM board
while powered.
CIM Installation Guidelines
The following guidelines offer a general outline for configuring and connecting the CIM units. You may have to
refer to other Keyscan documentation that was included with other components such as a NETCOM2P or
NETCOM6P – Reverse Network to complete the installation depending on how you are configuring the CIM
units.
If using a network connection, ensure that you program the NETCOM device as outlined in the documentation
included with your particular NETCOM unit.
Connect the CIM circuit board according to the communication and power diagrams.
Ensure that the EGND terminal on TB1 of each CIM is connected to an earth ground to protect the circuit board
and the system from high-voltage transients.
Set the jumpers accordingly on the CIM depending on whether it is a global master or slave, it is a terminating
CIM on the CANBUS, or it is CIM 0. Also, ensure the correct communication serial bit rates are correct. Refer to
the CIM Jumper Settings table.
Repeat connections and jumper settings for each control board and CIM.
Apply power to all CIM and ACU circuit boards.
Do one of the following procedures at the control board:
If this is an existing system, press reset S1 on the control board for board initialization.
If this is a new installation, press S1, wait 5 seconds, and then press S3 within ten seconds. Allow two
minutes for board initialization after clearing memory.
Return to a PC with the Client module, log on to the appropriate site, and perform a full upload.
CIM Connection Diagrams
Observe the diagrams on the following pages for connecting the CIM units to the access control boards and
connecting the CIMs with CAN Bus 1 and CAN Bus 2.
The CIM designated as CIM 0 supports serial or network (TCP/IP) to CANBUS 1 communication. The CIM unit
does not support modem communication.