Keyscan Inc. – Technical Guide (PC109x - 04.15)
38
Figure 25 – Terminate Input Wiring – Door Inputs (Contacts)
Cut View of CA8500B
Door Inputs - A
RTE Inputs - B
Door 1
8
to
Door
Input
1
Door Contact
to
Common
1K
Single end of line
supervision
to Door Input
1
Door Contact
to Common
1K
Double end of line
supervision
3K
Non-supervised
Notes
Diagram illustrates CA8500B. Connections
also apply to CA250B & CA4500B.
- CA250B
– up to 2 door inputs
- CA4500B
– up to 4 door inputs
- CA8500B
– up to 8 door inputs
Supervision level set in Client software:
System VII & Vantage
– Site Unit Setup
Aurora
– Hardware Setup
Supervision level applied to all door inputs, RTE inputs, and auxiliary inputs.
NC
COM
NC
COM
NC
COM
7
6
5
4
3
2
1
Common
8
7
6
5
4
3
2
1
AUX Inputs - C
8
7
6
5
4
3
2
1
Common
Common
AUX Inputs - D
16
15
14
13
12
11
10
9
Common
AUX Inputs - E
24
23
22
21
20
19
18
17
KI-00129E-10-13