In entrances with two sliding panels with anti-panic breakout
system (fixed at the sides or to the wall) the automation must
be installed on the outside to allow break-out in any position;
photocells must therefore be installed to ensure a motor STOP in
the event of breakout.
If there are semi-fixed side panels next to the sliding panels which
also have breakout function, instead of the STOP photocells it is
sufficient to install two electrical contacts which break the circuit
and cut out the sliding panels if the semi-fixed side panels are
opened (which will always occur in breakout of the sliding panels).
N.B. If just one pair of photocells is installed, they must be
mounted 50 cm above the ground. If two pairs of photocells are
installed, they must be mounted 20 and 100 cm above the ground.
Internal radar, external radar compliant with EN 16005
Max length [m]
Cable type
AS+
30
PVC LiYY 6x0.34mm²
AS-
COM
PHOTO
RADAR (INT/EXT)
TEST (1/2)
BUS Accessories (NO mechanical selector)
Max length [m]
Cable type
AS+
30
PVC LiYY TP (twisted pairs)
3x2x 0.5mm²
AS-
A
B
Mechanical selector
Max length [m]
Cable type
5
PVC LiYY 8x0.34mm²
2.4 - Mounting surface materials
TABLE OF FASTENERS FOR MOUNTING SURFACE TYPES
Mounting surface materials
Minimum thickness
Screw type
Steel
5mm
M8
Aluminium
6mm
M8
Aluminium
3mm
M8 threaded inserts
Reinforced concrete
>120mm in thinnest point
Expansion plugs Ø 14mm, M8 hex. head
screw
Plasterboard/hollow bricks
Must be reinforced with 5 mm steel structure
M8
Solid wood
50mm
Hex. head anchor bolt 13mm Ø 8mm
2.6 - Distanze di sicurezza
The protective measures regarding crushing and impact during the
opening movement can be considered applied to the danger points
if at least one of the following conditions is met, considering that
when most of the users are elderly, infirm, disabled and children,
door contact with the user is unacceptable:
a)
the panel travels parallel to a flat surface at a distance X ≤
100 mm from it and there is a safety distance Y ≥ 200 between
the secondary edge and the parts facing the room (see figure).
For telescopic doors, the measurement is made with reference
to the panel nearest to the room
crushing protection
2.5 - Assembly equipment
Before proceeding with assembly, be sure to have all the tools and
materials required to be able to install them with maximum safety,
in accordance with the current regulations. The figure shows some
examples of equipment for the installer.