33

EN

11.4 - Settings with special CODES

With the equipment off (without power) press the OK button and 

keep  it  pressed,  at  this  point  turn  on  the  equipment  (activate 

power), keeping the ok button pressed and after a few seconds 

the equipment emits a short acoustic signal. At this point, release 

the OK key, and the display will show: “0000”.

Using the P1 and P2 keys it is possible to modify the first two digits 

and the second two digits of the number separately, thus setting 

a  special  configuration  code,  which  must  then  be  confirmed  by 

pressing the OK key for two seconds.

Depending on the special code set, the following operations will 

be performed:

password 4444:

  A4 new KEY motor

password 2468:

  Start cyclic test mode

password 1234:  

Enabling of special displays

password 3223:

  Restart of parameters from 1 to 8 as

 

 

default according to the door weight class

password 9696:

 Restart of all parameters as

 

 

default settings. After the

 

 

restart, a learning is forced

password 8585:

  NT.I emergency closure (N.C.). With this

 

 

password the Y parameters is set  

 

 

at the value 3. It can then be changed from the  

 

 

keypad but not shown with value 3

Funzione

Default

Min

Max Valore

Note

N.

0

0

2

SLOW. PHOTO monitoring

0 = not monitored

1 = a monitored device

2 = two monitored devices

O.

0

0

2

STOP monitoring

0 = not monitored 

1 = a monitored device

2 = two monitored devices

P.

0

0

1

Battery presence

0 = battery not present

1 = battery present

R.

0

0

1

Lock if R.INT or R.EXT

0 = Normal operation 

1 = RINT or REXT lock closed door

T.

0

0

1

Radar Type

0 = normal radar

1 = 100Hz output Hotron radar

U.

0

0

9

START opening duration

0 = step-step 

from 1 to 9 (in tenths of seconds)

V.

0

0

9

Lock delay

from 0 to 9 (in tenths of seconds)

Y.

0

0

2

Interlock

0 = disabled

1 = enabled

2 = emergency opening

* After modifying the “Motion direction” parameter, the subsequent 

first opening and closing operations will be carried out at reduced 

speed.

The values may vary according to the weight class of the door.

11.2 - Obstacle detection

If the door encounters an obstacle during closing, it reopens 

immediately, remains open for the pause time and then closes 

again. Subsequent closure takes place slowing down near the point 

where the obstacle was detected. If the obstacle is encountered 

three consecutive times, the door remains stationary, pressing 

against it.

If the door encounters an obstacle during opening, it locks and 

remains stationary for the set pause time, then closes at reduced 

speed. Subsequent opening takes place slowing down near the 

point where the obstacle was detected.

Monitored safety devices, equipped with a stimulation input, can 

be connected to the STOP, PHOTO and PHOTO RALL inputs. 

An  unattended  device  or  a  monitored  device  or  a  series  of  two 

monitored devices can be connected to each of the three inputs. It 

is necessary to set the configuration of each individual input using 

parameters L, N and O (see Modification of parameters). In the 

case of the unattended device, the corresponding parameter must 

be set to the value 0. In this case, no device test is performed. 

In the case of a single monitored device, the corresponding 

parameter must be set to 1. In this case, the device test is carried 

out via the TEST 1 output, which connects to the test input of the 

monitored device. In the case of two monitored devices connected 

in series, the corresponding parameter must be set to the value 

2.  In  this  case,  testing  of  the  first  device  is  carried  out  through 

the TEST  1  output,  which  connects  to  the  test  input  of  the  first 

monitored device, and the test of the second device is performed 

through the TEST 2 output, which connects to the test input of the 

second monitored device. The tests are carried out immediately 

after the end of each door opening movement; if one of the tests 

fails,  the  corresponding  error  is  displayed  (see  Errors)  and  the 

door does not close. Every 30 seconds the test is repeated (in the 

case  of  opening  with  the  OPEN  command,  the  test  is  repeated 

upon receipt of the CLOSE command), and if it succeeds the door 

closes again. During this error state, it is still possible to move 

the selector to the Lock position and close the door by hand: two 

seconds after closing, the electric lock will be activated.

11.3 - Monitored safety devices

ATTENTION !

Содержание LEVANTE

Страница 1: ...s para su instalación y uso Instruções e advertências para a instalação e utilização Instrukcje i zalecenia dotyczące instalacji i użytkowania Operatore per porte automatiche scorrevoli Operator for Automatic Sliding Doors Opérateur pour portes coulissantes automatiques Antrieb für automatische Schiebetüren Actuador para puertas automáticas de corredera Operador para portas de correr automáticas N...

Страница 2: ...f SEL4 selector connection Example of SEL5 selector connection First start up Power on 10 10 1 10 2 10 3 10 4 10 5 10 6 10 7 10 8 10 9 10 10 10 11 10 12 10 13 10 14 10 15 10 16 10 17 10 18 10 19 10 20 Operating mode The operating modes Learning procedure Deceleration space self test procedure Bidirectional mode Output Mode Input Mode Partial Opening Mode Open Mode Block Mode Pharmacy Mode Open and...

Страница 3: ...ection Do not proceed with installation if any one of these devices is not suitable for its intended purpose check that the devices purchased are sufficient to guarantee system safety and functionality perform a risk assessment including a list of the essential safety requirements as envisaged in An nex I of the Machinery Directive specifying the so lutions adopted The risk assessment is one of th...

Страница 4: ...lowing complete disconnection in the conditions speci fied by class III overvoltage use unions with IP55 or higher protection when connecting hoses pipes or cable glands the electrical system upstream of the automation system must comply with the relevant regulations and be constructed to good workmanship stan dards this appliance can be used by children aged from 8 years and above and persons wit...

Страница 5: ... s for panel in weight class 0 Closing speed Adjustable max 50 cm s for panel in weight class 0 Opening pause time Adjustable from 0 to 60 seconds Operating temperature from 20 C to 55 C Protection rating IP 22 Crosspiece length max 7 m Fuse 1 power line 15A blade fuse type AL Auxiliary battery power supply fuse 15A blade fuse type AL Accessories power outlet 28V max with 500mA max Use in highly a...

Страница 6: ...YY 8x0 34mm 2 4 Mounting surface materials TABLE OF FASTENERS FOR MOUNTING SURFACE TYPES Mounting surface materials Minimum thickness Screw type Steel 5mm M8 Aluminium 6mm M8 Aluminium 3mm M8 threaded inserts Reinforced concrete 120mm in thinnest point Expansion plugs Ø 14mm M8 hex head screw Plasterboard hollow bricks Must be reinforced with 5 mm steel structure M8 Solid wood 50mm Hex head anchor...

Страница 7: ...se specified for the automation system in which the product is integrated Check that the mechanical safety stops required on the door are solid and properly installed Check that the product fixing area is not subject to flooding Heavy acidity or salinity conditions or proximity to sources of heat may cause product malfunction Incaseofextremeweatherconditions forexamplesnow ice sudden temperature c...

Страница 8: ...ll the dimensions of the following layouts are expressed in millimetres mm 4 1 Dimensions installation with commercial profile Side View 530PROF035A00 5 20 50 900PA024 hsp 10 900PA021 Ha H 6 hpa hsp regolazione 4 5 mm hpa 15 mm hsp 10 mm 6 4 5 4 5 mm hpa 168 min 47 min 30 Ha H 88 48 15 23 17 min 47 min 30 530PROF035A00 50 900PA024 900PA021 Ha H 6 hpa hpi hsp regolazione 4 5 mm hpa 15 mm hpi 30 mm ...

Страница 9: ... certified KIT 4 2 Dimensions installation with glass panels Side View hv H 6 36 7 regolazione 4 5 min 47 min 30 168 88 48 23 17 36 hv 90 H 14 40 6 4 5 4 5 mm 900PA005E 900PA008 7 min hv H 6 22 7 regolazione 4 5 min 47 min 30 168 48 23 17 hv 90 H 88 4 5 mm 14 40 6 4 5 900PA007 900PA008 7 min ...

Страница 10: ...m while for the screws in the ends it is recommended not to exceed 200 mm from the end edge of the beam Once all the holes have been drilled clean the beam well from the shavings and aluminium residues To fix the beam use screws appropriate to the type of support present with a diameter of not less than 6 mm and a head height of not more than 6 5 mm Max screw diameter Ø4 2 Coupling bracket 3 5 max...

Страница 11: ...600 2900 1400 750 50 440 2950 4200 3300 1600 850 50 540 3350 4800 3700 1800 950 50 640 3750 5400 4100 2000 1050 50 740 4150 6000 4300 2100 1100 50 790 4350 6300 OPEN OPEN 5 3 Installation dimensions for double panel version Top and front views Indications for installation of subgroups runner positions calculation of automation length and permitted limit measurements Corresponding to a useful passa...

Страница 12: ...25 Dtc 170 mm Lbelt 2 LTr 1310 Table of measurements of single panel standard beams with opening to the right LTr PL LA S B Ltot Lbelt 1900 900 970 40 30 1950 2500 2100 1000 1070 40 30 2150 2900 2500 1200 1270 40 30 2550 3700 2900 1400 1470 40 30 2950 4500 3300 1600 1670 40 30 3350 5300 3700 1800 1870 40 30 3750 6100 4100 2000 2070 40 30 4150 6900 4300 2100 2170 40 30 4350 7300 5 4 Installation di...

Страница 13: ...ngth Belt transmission position Belt length Table of measurements of single panel standard beams with opening to the left LTr PL LA S B Ltot Lbelt 1900 900 970 40 30 1950 2500 2100 1000 1070 40 30 2150 2900 2500 1200 1270 40 30 2550 3700 2900 1400 1470 40 30 2950 4500 3300 1600 1670 40 30 3350 5300 3700 1800 1870 40 30 3750 6100 4100 2000 2070 40 30 4150 6900 4300 2100 2170 40 30 4350 7300 OPEN LT...

Страница 14: ...ofile to size make the holes for the fixing screws of the panel at the appropriate notch on the adapter profile and fix the profile on the panel with the screws N B Be careful not to insert the screws at the runner fixings The runner is secured to the adapter profile by means of two fixing plates The following figure shows the mechanism for inserting the fixing plates onto the adapter profile N B ...

Страница 15: ...panel when closed Secure the plate to the floor using suitable expansion plugs and screws Once the panel is connected to the beam push the anti derailment wheels upwards and lock them N B It is advisable not to lock the anti derailment wheel directly in contact with the upper part of the beam profile but to leave approximately 0 5 1 mm of space between the wheel and the beam At this point it is po...

Страница 16: ...ack cable 22 M1 red cable It is important to respect the directions indicated In case the polarity is reversed the door will work in reverse The encoder cable connects to terminal CN4 as shown in the figure with the sequence BLACK cable WHITE cable A GREEN cable B RED cable 7 POSITIONING AND WIRING OF THE MODULES INSIDE THE BEAM secondary is passed into the appropriate guide above the motor and co...

Страница 17: ...n Once the two ends are joined connect the junction plate to the panel runner in the position indicated in the Installation Dimensions views from above and from the front section according to the type of door being installed 7 4 Tensioning the belt To tension the belt first proceed by loosening the two screws A and then apply the tension by tightening the screw B until reaching the pre set control...

Страница 18: ...e Connect the network cables to the line input terminal as shown in the image The line must be adequately protected against short circuits Fasten the 230 Vac cable with a cable tie to the hole below A 230 Vac L A N 8 1 Assembly of the side covers not on recessed versions The following figure shows the side covers in the two variants right R and left L where right means the cover that is mounted on...

Страница 19: ...he case of a beam embedded in the wall use the dedicated brackets of the LEV4 kit supplied separately Use the clip and screw supplied in the side covers to secure the beam 8 2 Recessed wall beam 8 3 Cover panel preparation The cover panel is equipped with a coupling that is used to keep the position open at 110 to allow maintenance interventions To insert the locking screws it is necessary to dril...

Страница 20: ... fixing clip FIG 3 40 cm 40 cm 40 cm To prepare the cover proceed as follows Holes for screws for fixing to the covers FIG 1 Drill two Ø5 5 holes on both ends of the panel 15 mm away from the edge Application of an anti vibration seal A and of the brush B FIG 2 Insert the brush B in the dedicated seat sliding it to the end of the cover The anti vibration seal A must be positioned at the ends and i...

Страница 21: ...RADAR INT radar input EXT RADAR EXT radar input PH2 SLOW PHOTO Input COM Common AS Accessories power supply 24Vdc AS Accessories power supply 24Vdc CN8 TEST2 Input test radar 2 TEST1 Input test radar 1 CLOSE Closure control input OPEN Opening control input COM Common AS Accessories power supply 24Vdc AS Accessories power supply 24Vdc CN7 IL O Input interlock 0 IL I Input interlock 1 COM Common int...

Страница 22: ...NETWORK 230Vac CONNECTOR FOR 868 MHz RADIO SELECTORS BOARD EARTH CONNECTOR FOR RECEIVING BOARD TRANS SEC FUSE BATTERY FUSE ENCODER BLACK WHITE GREEN RED PRIMARY 230Vac STANDARD 1 24 Vac 6A TRANSFORMER 230 Vac 150 VA 24 Vdc MOTOR ENCODER ENCODER CABLE ELECTRIC LOCK 12V 5W EN 22 ...

Страница 23: ...ONS SELECTOR TYPE PA025CT PA014IR EXTERNAL RADAR WITH SAFETY DEVICE TYPE PA025CT PA014IR ANY RADAR WITH RIGHT OPENING PROTECTION TYPE PA025CT PA014IR ANY RADAR WITH LEFT OPENING PROTECTION SENSOR CABLE SENSOR CABLE SENSOR CABLE SENSOR CABLE CAB CAB CAB CAB RED RED RED RED BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE GREEN GREEN GREEN GREEN YELLOW YELLOW YELLOW YELLOW BLUE BLUE BLUE BLUE GREY GR...

Страница 24: ...LOSED EMERGENCY MUSHROOM BUTTON AND OPTIONAL RESET DISPLAY FUNCTIONS SELECTOR TYPE PA025CT PA014IR EXTERNAL RADAR WITH SAFETY DEVICE AND TEST TYPE PA025CT PA014IR ANY RADAR WITH RIGHT OPENING PROTECTION TYPE PA025CT PA014IR ANY RADAR WITH LEFT OPENING PROTECTION SENSOR CABLE SENSOR CABLE SENSOR CABLE SENSOR CABLE CAB CAB CAB CAB RED RED RED RED BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE GREEN...

Страница 25: ...XT RAD COM COM PHOTO TRANSMIT INT RAD EXT RAD MANI FOLD COM AC DCfrom12to24V AC DCfrom12to24V N O N O N O N O COM COM COM COM MANIFOLD MANIFOLD MANIFOLD MANIFOLD TRANSMITTER TRANSMITTER TRANSMITTER TRANSMITTER TEST P TEST P TEST P TEST P TEST N TEST N TEST N TEST N RED RED BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE GREEN GREEN GREEN GREEN YELLOW YELLOW YELLOW YELLOW BLUE BLUE BLUE BLUE GREY G...

Страница 26: ...gnalling LED OPT Optional not used 1 Without manual selector 3 With complete selector Recommended installation With the connection with just 2 wires the following are lost LED error indication hardware reset connection of the EASY2terminal In order not to use the manual selector it is necessary to bridge the cn5 connector between the AS and R H connection 2 With 2 wire manual selector 9 8 Example ...

Страница 27: ...6 4 4 4 2 4 0 3 9 3 7 3 5 3 2 3 0 2 7 2 5 2 1 1 8 1 3 0 8 5 4 5 2 5 0 4 8 4 6 4 4 4 2 3 9 3 7 3 4 3 1 2 8 2 4 2 0 1 4 0 9 6 0 5 8 5 6 5 4 5 2 4 9 4 7 4 4 4 1 3 8 3 5 3 1 2 7 2 2 1 6 1 0 6 7 6 5 6 3 6 0 5 8 5 5 5 2 4 9 4 6 4 3 3 9 3 5 3 0 2 5 1 8 1 1 7 4 7 1 6 9 6 6 6 3 6 0 5 7 5 4 5 1 4 7 4 3 3 8 3 3 2 7 1 9 1 2 8 0 7 8 7 5 7 2 6 9 6 6 6 2 5 9 5 5 5 1 4 7 4 2 3 6 3 0 2 1 1 3 8 7 8 4 8 1 7 8 7 5 7 ...

Страница 28: ...riti ecc fossero variate dal precedente apprendimento 10 2 Learning procedure At any time by pressing and holding the down arrow key P2 for at least 2 seconds until the sounding of an acoustic signal the message APPR appears on the display and it is possible to command a learning manoeuvre This manoeuvre begins with a radar command and consists of six manoeuvres three openings and three closures d...

Страница 29: ...TART until the position of the selector is changed 10 10 Operation in Pharmacy mode Positioning the selector in the Pharmacy position results in closing of the door and subsequent activation of the electric lock Only the START OPEN and CLOSE commands are accepted The door opens only approximately 15 cm and the electric lock is activated again when closed This condition remains until the position o...

Страница 30: ...ing the power supply If the battery is faulty disconnected or completely discharged the equipment turns off for a few moments during the test and then turns on again This event is automatically stored and the test is no longer repeated in order to avoid further shutdown of the equipment every 4 hours If the battery voltage drops below 23 5 volts the E05 low battery error is signalled In this case ...

Страница 31: ... 1 100 amps if the door is in motion Max current of the last movement if the door is stopped UMOT Motor voltage in volts SOGO Obstacle current threshold in 1 100 amps UERR They are automatically displayed in sec intervals The codes of the last 16 errors that have occurred numbers from 1 the most recent to 16 the least recent TEMP The temperature of the power electronics is displayed in vn degrees ...

Страница 32: ...ing approach space 8 38 10 300 Closure approach space 9 16 1 100 Force on obstacle A 2 1 60 Permanence time sec B 75 50 99 Partial opening stroke percentage from 50 to 99 C 0 0 1 Electric lock type 0 monostable 1 bistable D 0 0 1 Adaptation to the traffic 0 not enabled 1 present E 0 0 2 If door forced 0 resists forcing 1 opens 2 remains free F 0 0 4 If there is no electricity 0 continues operation...

Страница 33: ...losing it reopens immediately remains open for the pause time and then closes again Subsequent closure takes place slowing down near the point where the obstacle was detected If the obstacle is encountered three consecutive times the door remains stationary pressing against it If the door encounters an obstacle during opening it locks and remains stationary for the set pause time then closes at re...

Страница 34: ...Flat battery The equipment stops E08 Motor polarity reversed or encoder channels reversed The equipment stops and will only attempt to resume opera tion after being reset or turned off E09 Weight detected higher than the max permissible The equipment will only attempt to resume operation after being reset or turned off E10 Motor current greater than the maximum permissible detected The equipment w...

Страница 35: ...adars and photocells Every 6 months or every 500 000 manoeuvres Door connected to the power supply Check the correct operation of the command and safety devices radar and photocells Check the stability of the doors during operation they must slide smoothly and evenly without fric tion and jolts If present check the correct operation of the electric lock and release If present check the condition o...

Страница 36: ...e of the person who commissioned it the serial number and year of construction and the CE marking on the gate or door also fit a plate specifying the procedure for releasing the system by hand the relevant regulatory requirements especially the EN12445 standard which specifies the test methods for gate and door automation systems check that all connected devices photocells sensitive edges emergenc...

Страница 37: ...37 EN NOTE ...

Страница 38: ......

Страница 39: ......

Страница 40: ...Key Automation S r l Via Meucci 23 30027 San Donà di Piave VE T 39 0421 307456 F 39 0421 65698 info keyautomation it www keyautomation it Instruction version 580LEV REV 02 EN ...

Отзывы: