24
EN
PARAMETERS
DESCRIPTION
DEFAULT
CONFIGURATION MIN MAX
UNIT
1
EL
.
F
.
Electric brake
0 = disabled
1 = enabled
0
0
100
x 0.01s
(steps of 5)
2
SP
.
h
.
PHOTO1 response on start-up from closed
0 = PHOTO1 check
1 = the gate also opens if PHOTO1 is engaged
1
0
1
3
Ph
.
2
.
PHOTO2 response
0 = Enabled in opening and closing OP/CL
1 = Enabled only in opening OP
0
0
1
4
tP
.
h
.
Photo device test
0 = disabled
1 = PHOTO1 enabled
2 = PHOTO1 enabled
3 = PHOTO1 and PHOTO2 enabled
0
0
3
5
ed
.
M
.
Type of edge
0 = contact (NC)
1 = resistive (82k)
0
0
1
6
iE
.
D
.
Edge intervention mode
0 = intervenes only on closing with inversion of direction
1 = stops automation (on opening and closing) and releases
the obstacle (short inversion)
0
0
1
7
tE
.
D
.
Edge test
0 = disabled
1 = enabled
0
0
1
8
LP
.
o
.
Pedestrian opening
30
0
100
% (steps
of 1)
9
TP
.
C
.
Automatic reclosing time from pedestrian (0 = disabled)
20
0
900
s
10
FP
.
r
.
Flashing light output configuration
0 = Steady
1 = Flashing
1
0
1
11
tP
.
r
.
Pre-flash time
(0 = disabled)
0
0
10
s
12
FC
.
Y
.
Courtesy light configuration
0 = At end of manoeuvre, lit for time TCY
1 = Lit if gate is not duration TCY
2 = Lit if courtesy light timer (TCY) not elapsed
3 = Gate open indicator on/off
4 = Gate open indicator proportional flashing
0
0
4
13
tC
.
Y
.
Courtesy light duration
0
0
900
s (steps
of 10s)
14
dE
.
A
.
Hold-to-run
0 = disabled
1 = enabled
0
0
1
15
se
.
r
.
Cycle threshold for assistance request. On reaching the set
threshold the subsequent cycles will be performed with
quick flashing (only if
FPr
is active).
(0 = disabled)
0
0
100
x 1000
cycles
16
se
.
f
.
Enabled in continuous flashing mode for assistance requests
(function only enabled when gate is closed).
0 = disabled
1 = enabled
0
0
1
17
HA
.
o
.
Water hammer on opening
0 = disabled
0
0
100
*100ms
18
HA
.
c
.
Water hammer on closing
0 = disabled
0
0
100
*100ms
19
mp
.
r
.
Interval for maintaining hydraulic motor pressure
0 = disabled
from 1 to 480 enabled as follows: 1 = 1 min. ON and 1 min
OFF, 2 = 1 min. ON and 2 min. OFF, ...
0
0
480
minutes
20
de
.
f
.
Reset to default values
6 - FURTHER DETAILS - ADVANCED MENU
The
ADVANCED MENU allows the system to be further customised
by modifying parameters not accessible from the basic menu
To access the ADVANCED menu, press the MENU key and hold it
down for 5 seconds
To modify ADVANCED MENU parameters, proceed as described
for the BASIC MENU
To set the default values: 1) access the advanced programming
function; 2) select the “dEf” parameter”; 3) activate the modification
mode (“0” on display”); 4) accept the modification (press “MENU”
and hold it down). A countdown should now appear: d80,d79...,d01
down to “
don
“. Release the key when finished.
n