EN

3 - PRELIMINARY CHECKS

2.4 - List of cables required

The cables required for connection of the various devices in a stan

-

dard system are listed in the cables list table.

Before installing the product, perform the following checks and in-

spections:

check that the gate or door is suitable for automation;

the weight and size of the gate or door must be within the operating 

limits specified for the automation system in which the product is 

installed;

check  that  the  gate  or  door  has  firm,  effective  mechanical  safety 

stops;

make sure that the product fixing zone is not subject to flooding;

high acidity or salinity or nearby heat sources might cause the pro-

duct to malfunction;

in case of extreme weather conditions (e.g. snow, ice, wide tempe-

rature variations or high temperatures), friction may increase, cau-

sing a corresponding rise in the force needed to operate the system; 

the starting torque may therefore exceed that required in normal 

conditions;

check that when operated by hand the gate or door moves smoothly 

without any areas of greater friction or derailment risk;

check that the gate or door is well balanced and will therefore re-

main stationery when released in any position;

check that the electricity supply line to which the product is to be 

connected is suitably earthed and protected by an overload and dif-

ferential safety breaker device;

the system power supply line must include a circuit breaker device 

with a contact gap allowing complete disconnection in the condi-

tions specified by class III overvoltage;

ensure that all the material used for installation complies with the 

relevant regulatory standards.

The  cables  used  must  be  suitable  for  the  type  of  installation;  for 

example, an H03VV-F type cable is recommended for indoor appli

-

cations, while H07RN-F is suitable for outdoor applications.

TECHNICAL SPECIFICATIONS:

Power supply (L-N)

230 Vac (+10% - 15%) 50-60 Hz 120 Vac (+10% - 15%) 50-60 Hz

Max motor load

700 W + 700 W

700 W + 700 W

Output for Vdc accessories power and device test power

24 Vdc 500 mA

24 Vdc 500 mA

Output for Vac accessories power

24 Vac 1 A

24 Vac 1 A

Courtesy light output

230 Vac 25 W

120 Vac 25 W

Flashing light output

230 Vac 25 W

120 Vac 25 W

Electric lock output

12 Vac / 15 VA

12 Vac / 15 VA

Maximum work time with settable nominal load

Adjustable

Adjustable

Pause time

Adjustable 0-900 sec.

Adjustable 0-900 sec.

Operating temperature

-20 °C + 55 °C

-20 °C + 55 °C

Power supply line fuses

6,3AF

6,3AF

Accessory fuses

 

DC

500mAF

500mAF

Accessory fuses

 

AC and electric lock

2AF

2AF

* If the power cable is longer than 30 m, a cable with a larger cross-section is required (3x2.5 mm

2

) and safety earthing is necessary in the 

vicinity of the automation.

** Two cables of  2 x 0.5 mm

2

 can be used as an alternative 

ELECTRIC CABLE TECHNICAL SPECIFICATIONS:

Connection

cable

maximum allowable limit

Power supply line

1 x cable 3 x 1,5 mm

2

20 m *

Motor power supply line

1 x cable 4 x 1,5 mm

2

20 m

Flashing light, 

courtesy light

Antenna

1 x cable 4 x 0,5 mm

**

1 x cable type RG58

20 m

20 m (advised < 5 m)

Electric lock

1 x cable 2 x 1 mm

2

20 m

Transmitter photocells

1 x cable 2 x 0,5 mm

2

20 m

Receiver photocells

1 x cable 4 x 0,5 mm

2

20 m

Sensitive edge

1 x cable 2 x 0,5 mm

2

20 m

Key-switch

1 x cable 4 x 0,5 mm

2

20 m

Содержание CT202

Страница 1: ...para dois motores 230 Vac 120 Vac para portões de batente Centrala dla dwóch silników 230 Vac 120 Vac do bram skrzydłowych CT202 Istruzioni ed avvertenze per l installazione e l uso Instructions and warnings for installation and use Instrucciones y advertencias para su instalación y uso Anleitungen und Hinweise zu Installation und Einsatz Instruções e advertências para a instalação e utilização In...

Страница 2: ... Product Electric connections Display during normal operation Autolearning of the travel stroke Customising the system BASIC MENU Connecting the radio receiver Testing and commissioning Testing Commissioning Further details ADVANCED MENU Instructions and warnings for the final user EC declaration of conformity pag 15 pag 16 pag 16 pag 16 pag 16 pag 17 pag 17 pag 18 pag 18 pag 19 pag 20 pag 22 pag ...

Страница 3: ...e with the following safety precautions never make any modifications to part of the automation system other than those specified in this manual Operations of this type can only lead to malfunctions The manufacturer declines all liability for damage caused by unauthorised modifications to products do not allow parts of the automation system to be immersed in water or other liquids During installati...

Страница 4: ... DOWN pushbutton 12 SS STEP STEP pushbutton 13 Safety device dip switch 14 F3 Safety fuse for AC accessories electric lock 2 A quick acting 15 F2 Safety fuse for DC accessories 500 mA quick acting 16 F1 Safety fuse for power line 6 3 A quick acting 2 3 Models and technical characteristics CT202 control unit is equipped with a display to enable simple pro gramming and constant monitoring of input s...

Страница 5: ...s III overvoltage ensure that all the material used for installation complies with the relevant regulatory standards The cables used must be suitable for the type of installation for example an H03VV F type cable is recommended for indoor appli cations while H07RN F is suitable for outdoor applications TECHNICAL SPECIFICATIONS Power supply L N 230 Vac 10 15 50 60 Hz 120 Vac 10 15 50 60 Hz Max moto...

Страница 6: ...OP Eliminates the need to bridge the terminal board inputs WARNING with the dip switch ON the safety devi ces are disabled 4 1 Electrical connections WARNING Before making the connections ensure that the control unit is not powered up 2 3 4 1 1 2 TX RX NC PH2 2 3 4 1 1 2 TX RX PH1 N L 24 Vdc 24 Vac 24 Vac EL EL GND 24 TX PH EDGE EDGE PH2 PH1 STOP OPEN CLOSE PED SS COM L N UP DOWN MENU SS COURTESY ...

Страница 7: ... device the contact can be deactivated at any time cutting out the automation system and disabling all functions including Automatic Closure OPEN OPEN command NO contact between OPEN and COM Contact for the HOLD TO RUN function The gate OPENS as long as the contact is held down CLOSE CLOSE command NO contact between CLOSE and COM Contact for the HOLD TO RUN function The gate CLOSES as long as the ...

Страница 8: ...UTION if manual programming of deceleration intervals is required go to the next table 1 CAUTION check that mechanical end stops compulsory are present and secure The motors must always reach the mechanical end stop 2 Move the gate manually to mid travel 3 Press the pushbuttons UP and MENU at the same time for at least 5 seconds until LOP is displayed then if necessary press DOWN see figure Ensure...

Страница 9: ...n press the SS command Motor M2 stops and motor M1 starts in closing 9 On reaching the point where motor M1 closing deceleration is required press SS M1 motor move ment continues at low speed 10 Precisely when motor M1 reaches the closed position press the SS command Motor M1 stops and restarts in opening 11 On reaching the point where motor M1 opening deceleration is required press SS M1 motor mo...

Страница 10: ...MENU If necessary users may select a BASIC MENU which allows modi fication of the control unit s basic parameters To select the BASIC MENU proceed as described below WARNING to be certain of accessing the NORMAL OPERATION display state the starting point for accessing the BASIC MENU press the MENU key twice n PARAMETERS DESCRIPTION DEFAULT CONFIGURATION MIN MAX UNIT 1 TCL Automatic reclosing time ...

Страница 11: ...g its opening travel and automatic closure is disabled to re start operation the user must press the control button or use the transmitter 5 TESTING AND COMMISSIONING THE AUTOMATION SYSTEM 5 1 Testing All system components must be tested following the procedures de scribed in their respective operator s manuals ensure that the recommendations in Chapter 1 Safety Warnings have been complied with ch...

Страница 12: ...or proportional flashing 0 0 4 13 tC Y Courtesy light duration 0 0 900 s steps of 10s 14 dE A Hold to run 0 disabled 1 enabled 0 0 1 15 se r Cycle threshold for assistance request On reaching the set threshold the subsequent cycles will be performed with quick flashing only if FPr is active 0 disabled 0 0 100 x 1000 cycles 16 se f Enabled in continuous flashing mode for assistance requests functio...

Страница 13: ... or power failures while waiting for the engineer to come or for the power to be restored if your system is not equipped with buffer batteries the door or gate can be used just like any non automated installation To do this the manual release procedure must be carried out manual release and operation first bear in mind that the release procedure can only be carried out with the door or gate statio...