5
DEFINITIONS
INPUT
- INPUT; This section of the program menu assigns the type of input the unit will be using (4-20 mA, 0-5 V, 0-10 V,
1-5 V, Linear or square root extraction).
I 4-20
- I 4-20; This sets the unit for a current input of 4 to 20 mA.
E 1-5
- E 1-5; This sets the unit for a voltage input of 1 to 5 volts.
E 0-5
- E 0-5; This sets the unit for a voltage input of 0 to 5 volts.
E 0-10
- E 0-10; This sets the unit for a voltage input of 0 to 10 volts. (0-20 mA input is available using this setting and the
current (I) input pin 4)
RELAYS
- RELAYS; This section of the program menu sets the control output variables (relays & open collector).
HYS A
- HYSTERESIS FOR OUTPUT A; This value is the number of units below Preset A that the output will remain "ON".
EXAMPLE: Preset A set at 100, Hys set at 10. Output A will activate (turn on) when the rate equals 100; Output
A will deactivate (turn off) when the rate falls below 90 (10 below Preset A)
HYS B
- HYSTERESIS FOR OUTPUT B; Same as HYS A.
LOC
- LOCK; This section of the program menu sets up the lockout type and code. (to lock or unlock, press the "A" key
when in run mode. see pg.10)
LC ALL
- LOCK ALL; When this is selected the lockout will lock the program as well as the Presets and reset button. The
presets can be viewed but not changed.
LC PG
- LOCK PROGRAM; When this is selected the lockout will lock only the program. The Reset can be activated and
the presets can be viewed and changed.
CODE
- CODE; This is a 5-digit code which will be used to lock and unlock the front panel.
SETUP
- SETUP; This section of the program menu sets up the operating variables.
DECLOC
- DECIMAL LOCATION; This allows the user to program a decimal point.
SET LO
- SET LOW; This is the display value (-9999 to 49999) for the lowest input (0 or 1 Volts; 4 mA).
(i.e. 4 mA = -10
°
)
SET HI
- SET HIGH; This is the display value (-9999 to 49999) for the highest input (5 or 10 Volts; 20 mA). (i.e. 20 mA =
100
°
)
LO CUT
- LOW CUT-OFF; This is the lowest display value (-9999 to 49999) to be recognized. All readings below this
value will assume the "set lo" value, even if the "set lo" is higher than the "set hi" value..
NOR
- NORMALIZING FACTOR; This is an averaging factor (00.0 to 99.9). Higher settings provide more normalizing
(averaging) for a more stable display. Derived from the equation:
(OLD DATA x "NOR" + NEW DATA)
("NOR" + 1)
opt
- OPTIONS; This section of the program menu is for setting up optional features (analog out, RS232/422 serial
communications).
out lo
- OUT LOW; The displayed value (-9999 to 49999) at which the unit will output 4 mA (-10
°
= 4 mA out).
Содержание INTELLECT-69PM2
Страница 4: ...THIS PAGE IS BLANK...