DEFINITIONS

INPUT

 - INPUT; This section of the program menu assigns the type of input the unit will be using (4-20 mA, 0-5 V, 0-10 V,

1-5 V, Linear or square root extraction).

I 4-20

 - I 4-20; This sets the unit for a current input of 4 to 20 mA.

E 1-5

 - E 1-5; This sets the unit for a voltage input of 1 to 5 volts.

E 0-5

 - E 0-5; This sets the unit for a voltage input of 0 to 5 volts.

E 0-10

 - E 0-10; This sets the unit for a voltage input of 0 to 10 volts. (0-20 mA input is available using this setting and the

current (I) input pin 4)

RELAYS

 - RELAYS; This section of the program menu sets the control output variables (relays & open collector).

HYS A

- HYSTERESIS FOR OUTPUT A; This value is the number of units below Preset A that the output will remain "ON".

EXAMPLE: Preset A set at 100, Hys set at 10.  Output A will activate (turn on) when the rate equals 100; Output
A will deactivate (turn off) when the rate falls below 90 (10 below Preset A)

HYS B

- HYSTERESIS FOR OUTPUT B; Same as HYS A.

LOC

 - LOCK; This section of the program menu sets up the lockout type and code. (to lock or unlock, press the "A" key

when in run mode.  see pg.10)

LC ALL

 - LOCK ALL; When this is selected the lockout will lock the program as well as the Presets and reset button.  The

presets can be viewed but not changed.

LC PG

 - LOCK PROGRAM; When this is selected the lockout will lock only the program.  The Reset can be activated and

the presets can be viewed and changed.

CODE

 - CODE; This is a 5-digit code which will be used to lock and unlock the front panel.

SETUP

 - SETUP; This section of the program menu sets up the operating variables.

DECLOC

 - DECIMAL LOCATION; This allows the user to program a decimal point.

SET LO

 - SET LOW; This is the display value (-9999 to 49999) for the lowest input (0 or 1 Volts; 4 mA).

 (i.e. 4 mA = -10 

°

)

SET HI

 - SET HIGH; This is the display value (-9999 to 49999) for the highest input (5 or 10 Volts; 20 mA).  (i.e. 20 mA =

100 

°

)

LO CUT

 - LOW CUT-OFF; This is the lowest display value (-9999 to 49999) to be recognized.  All readings below this

value will assume the "set lo" value, even if the "set lo" is higher than the "set hi" value..

NOR

 - NORMALIZING FACTOR; This is an averaging factor (00.0 to 99.9).  Higher settings provide more normalizing

(averaging) for a more stable display.  Derived from the equation:

(OLD DATA x "NOR" + NEW DATA)

("NOR" + 1)

opt

 - OPTIONS; This section of the program menu is for setting up optional features (analog out, RS232/422 serial

communications).

out lo

 - OUT LOW; The displayed value (-9999 to 49999) at which the unit will output 4 mA (-10

°

 = 4 mA out).

Содержание INTELLECT-69PM2

Страница 1: ...MONITOR INSTALLATION OPERATING INSTRUCTIONS MODELS INT 69PM2 99319 12 19 00 KESSLER ELLIS PRODUCTS CO 10 Industrial Way East Eatontown NJ 07724 Telephone 732 935 1320 Toll Free 800 631 2165 Fax 732 93...

Страница 2: ...nternal circuit boards or devices Handling Procedure 1 Power to unit must be removed 2 Personnel must be grounded via wrist strap or other safe suitable means before any printed circuit board or other...

Страница 3: ...ON SPECIFICATIONS 2 MOUNTING 3 WIRING 4 DEFINITIONS 5 FRONT PANEL OPERATIONS 7 PROGRAMMING FLOWCHART 7 PROGRAMMING 8 SETTING PRESETS PANEL LOCK 11 RS232 RS422 OPERATIONS 12 RS232 RS422 WIRING 16 TROUB...

Страница 4: ...THIS PAGE IS BLANK...

Страница 5: ...nal line fuse is recommended Add or replace the external fuse with the following specified type and rating only Input Power Recommended Fuse 115 VAC 100 mA slow blow fuse 230 VAC 50 mA slow blow fuse...

Страница 6: ...0mA in ON state Input Linear 4 20mA 0 5V 0 10V or 1 5V selectable from the front panel Input Impedance Current 100 Voltage 115K Calibration The unit does all of the calibrations internally There are n...

Страница 7: ...through the rubber gasket Insert the unit into the panel Slide the brackets up the groove to press against the back of the panel as shown in FIG A Insert the screws into the rear of the brackets Tight...

Страница 8: ...ires are not run into the unit in a bundle with power input lines We recommend using shielded cable Con nect the shield to DC ground of the unit and earth at one point in the circuit preferably at the...

Страница 9: ...he lockout will lock the program as well as the Presets and reset button The presets can be viewed but not changed LC PG LOCK PROGRAM When this is selected the lockout will lock only the program The R...

Страница 10: ...t list the unit will transmit the present peak value when the strobe is acti vated UALLEY VALLEY When this is added to the print list the unit will transmit the present valley value when the strobe is...

Страница 11: ...h PRO GRAM choices Press to step through set up choices in program mode iNPUT i 4 20 E 0 5 E 1 5 E 0 10 RUN MODE RELAYS HYS A HYS B XXXXX RUN MODE LOC LC ALL LC PG CODE RUN MODE SETUP DECLOC SET LO SE...

Страница 12: ...xisting HyS A value XXXXX HYS B PRGM PRGM ENTER This section of the menu sets up the open collector outputs and or relays Hys hysteresis The number of units below the preset that the output will remai...

Страница 13: ...e value press the A button until the digit passes 4 a nega tive sign will appear SET HI Display value for the highest input 5 or 10V 20mA i e 20mA 100 Key in the desired high value and press RST ENTER...

Страница 14: ...ID number This ID number 1 to 99 must be addressed to bring the unit on line If the unit number is set at 00 the unit cannot be addressed Key in the desired unit number and press RST ENTER to enter d...

Страница 15: ...ayed value is not the desired preset press the key s under the digit to be changed To enter a negative value press the A button until the digit passes 4 a negative sign will appear Key in the lock cod...

Страница 16: ...2400 or 9600 are available Select the desired baud rate from the menu see step 5 of the programming section PRINT LIST The serial interface card is equipped with a strobe line When the strobe line is...

Страница 17: ...A Type Z B Type O Code F Decimal POSSIBLE COMMANDS Each command must be followed by a carriage return for execution DXX device unit ID Unit XX will come on line and stay on line until another device...

Страница 18: ...set dur B or hys B Sets dur B or hys B at requested value dur B when B is assigned to total hys B when B assigned to rate EI examine dur B or hys B Unit will transmit present dur B or hys B value i e...

Страница 19: ...t data before the return enter is sent Once a return enter is sent the unit begins processing the data and will transmit the requested data on a non priority basis over the data transmit line The unit...

Страница 20: ...ould be made as follows DB 9 CONNECTOR COMPUTER Transmit data pin 2 Receive data Receive data pin 3 Transmit data Ground pin 5 Ground PRINTER HOOKUP When connecting the unit to a printer you must firs...

Страница 21: ...ncorrect 2 High and low scaling set tings are incorrect 3 Transmitting device is de fective 4 Unit is defective 1 Input wiring is incorrect 1 Recheck power wiring 1 Use a different power sup ply or in...

Страница 22: ...ur warranty repair modification or returned goods process please contact your local distributor WARRANTY This product is warrantied against defects in materials and workmanship for a period of two 2 y...

Отзывы: