13
COMMANDS:
Each command consists of an instruction and an
address. Each instruction and address is repre-
sented by a letter. The prefix of each command
must be an instruction followed by an address (and
address variable if applicable). Note: These com-
mands are for general purpose units. Disregard
commands and data not relevant to this process
monitor.
INSTRUCTIONS (1st letter of command):
[S] Set - Used to set the value or operating param-
eter of an address. (i.e. “SC 5000” will set the
count at 5000)
[E] Examine - Used to examine the value or status
of an address. (i.e. “ER” will examine the
present rate reading)
[L]*List - Used to set the print list. (i.e. “LCRVA”
will set the list for count, rate, valley and preset
A. These values will be transmitted whenever
the strobe is activated.)
ADDRESSES (2nd letter of command):
[C]*Count
[R]*Rate
[P]*Peak
[V]*Valley
[A]*Pre A
[B]*Pre B
[L]*Low Set
[H]*High Set
[J] Low Out
[K] High Out
[N] Norm
[D] Unit #
[E] Input
[G] H/D A
[I] H/D B
[M] Time
[T] Baud
[W] Lock
[X] Meter
[Y] A Type
[Z] B Type
[O] Code
[F] Decimal
POSSIBLE COMMANDS:
Each command must be followed by a carriage
return for execution.
DXX: (device “unit ID” #)- Unit XX will come “on
line” and stay “on line” until another device is
addressed.
SD XX: (set device “unit ID”#)- sets unit ID # at
requested value
ED: (examine device)- Unit will transmit the present
device (unit ID) number (i.e. d = 000000XX).
SC XXXXXX: (set count)- Sets count at requested
value.
EC: (examine count)- Unit will transmit the present
count value ( i.e. c=00XXXXXX).
RC: (reset count)- Resets the counter, the control
output will not be reset. (If this feature is needed,
consult factory).
ER: (examine rate)- Unit will transmit the present
rate value (i.e. r= 000XXXXX).
RR: (reset rate)- Resets the normalization
EP: (examine peak)- Unit will transmit the present
peak value (i.e. p= 000XXXXX).
RP: (reset peak)- Unit will reset the peak.
EV: (examine valley)- Unit will transmit the present
valley value (i.e. v=000XXXXX).
RV: (reset valley)- Resets the valley.
SA XXXXX: (set preset A)- Sets preset A at re-
quested value. (-9999 to 49999)
EA: (examine preset A)- Unit will transmit present
preset A value (i.e. a=000XXXXX).
SB XXXXX: (set preset B)- Sets preset B at re-
quested value. (-9999 to 49999)