32
5. Installation and assembly
The telescopic KESSEL upper section
must be shortened to such an extent that all installed parts are
easy to service. Before insertion, chamfer by 15° to avoid da-
mage to the sealing gasket, the upper section can be inclined
by up to 5°. Then insert the upper section into the opening of
the separator and move it to the required position. With the aid
of the existing clamping ring it is now possible to fasten the
upper section in the desired position (alignment with the top
ground surface). The fine adjustment to the final height is then
effected with the adjusting screws. A ground slope can be com-
pensated for with the continuously height-adjustable and up to
5° inclinable attachment piece. The upper section must be lined
sufficiently and made flush with the ground level using a flat-
bed vibrator and a steel plate placed over the upper section.
For larger installation depths, the special KESSEL adapter (art
no. 917402), installation height 400 mm , must be used.
Remaining filling
For installation in areas driven over by trucks (cover Class D), a
reinforced concrete plate must be designed as the uppermost
layer. A respective formwork plan and reinforcement drawing
can be provided by KESSEL.
15°
(Dichtlippen fetten)
Auf der Rückseite der
Dichtung nicht
fetten
Lippendichtung DN 600
1
0
0
teleskopisches
Aufsatzstück
Mindestein-
stecktiefe
Behälterdom
mind. 20cm Freiraum
Wenn das
Aufsatzstück
gekürzt wird
muss eine
15° x 20 mm Fase
angebracht werden.
min. 20 cm of free space
Telescopic upper section
Lip seal DN 600
Minimum insertion depth
of upper section
Grease sealing lips (only grease inside the seal)
Do not grease on the
exterior side of the seal
Tank dome
If the upper
section needs
to be shorte-
ned, cut at a
15° angle as
shown.