KERR KD Gemini Скачать руководство пользователя страница 7

KD GEMINI – INSTALLATION/OPERATION MANUAL 

 

KD Gemini

 

 

 

May-06 

6

DRAFT CONTROL 

Use approved draft control supplied for 5” pipe.  Use two draft 
controls on strong draft chimneys.  Set specified draft pressure to   
-0.04” wc.  

Not applicable to Direct Vent installations

.

 

 

3.6  ASSEMBLE & INSTALL BURNER 

 

ASSEMBLE

 

Check burner model is correct for furnace rating required.  

BURNER

    

Assemble as per burner manufacturer’s instructions.   

 

SET END CONE 

Riello – Set turbulator as per furnace operating decal. 

 

 

Beckett – See Burner Manufactures Instructions. 

 

SELECT NOZZLE 

Select oil input, nozzle required and burner configuration as shown 
on furnace operating decal. 

 

INSTALL NOZZLE 

Install selected nozzle, check for clean seating and tighten in 
nozzle adaptor. 

 

CHECK 

 

See burner manufacturer’s instructions for correct setting. 

ELECTRODES

 

 

INSERTION

 

See “GENERAL SPECIFICATIONS” or diagram (Figure – 1).

  

LENGTH

 

 

MOUNT BURNER 

Tighten top nut first so  burner tips down slightly.  The burner is 
always installed in an upright position by four nuts. 

 

PUMP BY-PASS 

For one pipe system factory setting  (no plug).

  

PLUG 

 

WIRING

 

Refer to wiring diagram or wiring decal for correct burner 
connections.

 

Riello series burners use the Riello LT-1 thermostat 

relay or Honeywell R8038 relay. 

 

 

 

THERMOSTAT 

Connect thermostat terminals. 

 

DO NOT

 start the oil burner until installation is complete and all cleanout covers are 

secured in place. 

 

3.7  CHANGING NOZZLE

 

 

NOZZLE

 

If a new nozzle of a different size is installed, change the heating 

CHANGE 

blower speed according to the “BURNER SPECIFICATIONS” or 
operating decal. 

 
 
 
 
 
 
 
 

Содержание KD Gemini

Страница 1: ...AT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA Std B140 0 Std...

Страница 2: ...ement Venting Ventilation 5 3 5 Installation 5 3 6 Assemble Install Burner 6 3 7 Changing Nozzle 6 3 8 Set Up Burner For Efficient Operation 7 3 9 Blower Settings 8 3 10 Cooling AC Models 8 3 11 Humid...

Страница 3: ...se new approved disposable filters of the same size and type or clean permanent filters according to manufacturer s instructions Replace the filters or clean the filters more often if dusty conditions...

Страница 4: ...hat has been shut down for an extended period of time INSPECTION Have the furnace system serviced and inspected by a qualified technician CHECK Furnace system has not been tampered with FUEL ON Turn o...

Страница 5: ...ANY OTHER APPLIANCE 3 3 INSTALLATION CODES INSTALLATION MUST COMPLY WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION All local and national codes governing the installation of oil burning equ...

Страница 6: ...g decal for approved vent flue pipe sizes Maximum flue gas temperature is 575 F THROUGH THE This Furnace is approved for Kerr Direct Vent WALL VENTING COMBUSTION Install openings and ductwork to the f...

Страница 7: ...heck for clean seating and tighten in nozzle adaptor CHECK See burner manufacturer s instructions for correct setting ELECTRODES INSERTION See GENERAL SPECIFICATIONS or diagram Figure 1 LENGTH MOUNT B...

Страница 8: ...a stable symmetrical flame After 15 minutes of normal operation check SMOKE for 0 trace reading and measure CO2 Re adjust the burner controls as required When the burner is set lock the adjustments wi...

Страница 9: ...nty 3 12 THERMOSTAT ANTICIPATOR SETTING Thermostat anticipator setting should be 0 2 amps for any burner Check that the thermostat anticipator setting matches the primary control circuit current draw...

Страница 10: ...struction and the heating system tested on a long burn cycle 7 If the block vent switch shuts down the system check to ensure there is enough draft in the chimney and venting pipes 3 14 FAN CONTROL LI...

Страница 11: ...tight as possible Use a pipe joint compound suitable for oil on all pipe threads To reduce possibility of air leaks tighten stem packing gland nut on any valves installed in the suction line Also be s...

Страница 12: ...5 2 84 0 60 60B 3 5 0 0 88 000 26 850 950 4 3 0 92 3 48 0 75 60W 150 5 0 1 5 105 000 31 1080 1200 3 2 KDF R E 115 A3 Riello 40 F3 1 00 3 81 0 75 60W 175 5 0 1 5 116 000 34 1080 1300 3 1 KDF R E 130 A3...

Страница 13: ...2 wc External static AC 0 5 wc Cooling Air Flow 3 tons Maximum air temperature rise 85 F Fan Control 130 F ON 100 F OFF High Limit max design outlet temp 200 F 1 3 hp 1 speed 0 50 static 1300 CFM MOT...

Страница 14: ...fied for use with Kerr Direct Vent Certified for use with Kerr KPV SS1C through the wall mechanical vent system 10 0 TROUBLE SHOOTING GUIDE Furnace will not start Tripped blocked vent switch Clear ven...

Страница 15: ...hrough Change or insulate ductwork Unheated spaces Low speed switch is on Switch off blower low speed FAN OFF set low Fan control Set FAN OFF higher Motor speed set too high Reset motor speed to slow...

Страница 16: ...__________________________ START UP TEST RESULTS Nozzle ________________________________________ Pressure _______________________________________________ Air __________________________________________...

Страница 17: ......

Страница 18: ...KDF 14A Filter Frame Assembly K00 CB 0025 00 KDF 15 Rear Cabinet Top KD KC KD0 CB 0020 00 KDF 16 Blower Door 3BU 10 00DD 00 KDF 17 Delhi GT10 DD Blower 4CA 00 505M 23 KDF 18A Motor Run Capacitor 5 mi...

Страница 19: ......

Страница 20: ...KDR 14A Filter Frame Assembly K00 CB 0024 00 KDR 15 Rear Cabinet Top KD0 CB 0020 00 KDR 16 Blower Door K00 CB 0103 00 KDR 17 5 Flue Pipe Collar 3BU 10 00DD 00 KDR 18 Delhi GT10 DD Blower 4CA 00 505M 2...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Отзывы: