1-2
KLN 750W 121912
1.3
SPECIFICATIONS
Table 1-1 below indicates parameters that vary for different KLN 750W models; Table 1-2 lists
general specifications that apply to all KLN 750W models.
TABLE 1-1. KLN 750 WATT MODEL PARAMETERS
Model
(8)(9)(11)(12)
d-c Output Range
Ripple
(3)
Line Regulation
(5)
Load Regulation
(10)
Response Time
(7)
Remote
Sense
Voltage
drop
(max.)
Constant
Voltage
(CV)
(1)
Constant
Current
(CC)
(2)
CV
CC
(4)
CV
CC
CV
(6)
CC
(6)
Full
Load
Up
Full
Load
Down
No
Load
Down
V d-c
A d-c
mV
rms
mA
rms
0.05%
mV
0.1%
mV
0.05%
mV
0.1%
mV
Sec
Sec
Sec
V
KLN 6-100
0 to 6
0 to 100
10
180
2.8
11
2.8
23
0.08
0.05
0.6
1
KLN 8-90
0 to 8
0 to 90
10
180
2.8
11
2.8
23
0.08
0.05
0.6
1
KLN 20-38
0 to 20
0 to 38
10
76
4
5.8
4
12.6
0.08
0.05
0.8
1
KLN 30-25
0 to 30
0 to 25
10
63
5
4.5
5
10
0.08
0.08
0.9
1.5
KLN 40-19
0 to 40
0 to 19
10
48
6
3.9
6
8.8
0.08
0.08
1
2
KLN 60-12.5
0 to 60
0 to 12.5
10
38
8
3.25
8
7.5
0.08
0.08
1.1
3
KLN 80-9.5
0 to 80
0 to 9.5
10
29
10
2.95
10
6.9
0.15
0.15
1.2
4
KLN 100-7.5
0 to 100
0 to 7.5
10
23
12
2.75
12
6.5
0.15
0.15
1.5
5
KLN 150-5
0 to 150
0 to 5
16
18
17
2.5
17
6
0.15
0.15
2
5
KLN 300-2.5
0 to 300
0 to 2.5
25
13
32
2.25
32
5.5
0.15
0.15
3
5
KLN 600-1.25
0 to 600
0 to 1.25
75
8
62
2.13
62
5.26
0.25
0.3
4
5
NOTES:
1. Actual output voltage should be
≤
0.1% of rated voltage when output voltage is set to zero.
2. Actual output current should be
≤
0.1% of the rated current when output current is set to zero (resistive load).
3. Measured when output is within 10%-100% of rated value; ripple bandwidth: 300kHz (rms), noise bandwidth: <20MHz (p-p).
4. For 6V model: measured when output voltage 2-6V and rated current; all other models measured when output 10-100% of rated voltage and rated
current.
5. Input voltage 100-240V a-c, 50/60Hz.
6. Constant input voltage and output from 10% of loading to full load.
7. With rated input, resistive load.
8. Rated power output with input 115V or 230V a-c
9. Specifications met after 30 minutes of operation, ambient temperature 23±5°C, humidity under 80% R. H, a-c input voltage ±5% of nominal, THD
≤
2%, not using the remote compensation, not operating in series or parallel.
10. For example, the spec for KLN 6-100 line regulation and load regulation in CV mode is 0.05% + 2.8mV (or 6 x 0.0005 = ±3mV +2.8mV =5.8mV), so
line and load regulation are within 0.2mV to 5.8mV for the 6V model.
11. Add G suffix for models with optional GPIB interface, add E suffix for optional LAN interface.
12. Specifications subject to change without notice.
Содержание KLN 100-7.5
Страница 2: ......
Страница 4: ......
Страница 16: ...1 6 KLN 750W 121912 FIGURE 1 2 KLN 750W POWER SUPPLY OUTLINE DRAWING TWO UNITS MOUNTED IN RACK SHEET 1 OF 2...
Страница 36: ......
Страница 72: ......
Страница 86: ...Via Acquanera 29 22100 Como tel 031 526 566 r a fax 031 507 984 info calpower it www calpower it...