LEVELtrol-II Installation & Operating Instructions
Sub-menus
Display
Notes
6.4.11
SETUP PROCESS
INPUTS
(Compensation
Input)
SETUP PROCESS INPUTS
Level
Compen/Input
COMPENSATION INPUT
None Dens
Temp
COMP. INPUT SIGNAL
Voltage Current RTD
INPUT SIGNAL RANGE
0-10V 0-5V 1-5V
INPUT SIGNAL RANGE
4-20mA 0-20mA
COMP. LOW SCALE
10 F
COMP. FULL SCALE
110 F
COMP. DEFAULT
60.0 F
Advance To
SET FLUID PROPERTIES
Press ENTER when Compen/Input is flashing
to configure the Compensation Input.
Select Temperature to set the Compensation
Input for Temperature inputs.
Choose Temperature Signal Type.
Advance to "Temp To Use if Input Fail", if RTD
selected.
If Voltage selected,
Choose desired Voltage Range. Skip if RTD.
If Current selected,
Choose desired Current Range. Skip if RTD.
Enter the low temperature scale corresponding
to the low temperature signal. Skip if RTD.
Enter the high temperature scale
corresponding to the high temperature signal.
Skip if RTD.
Enter the Default Temperature.
The unit will use this value if the temperature
input fails.
NOTE:
When Density
(Dens) is selected,
The menu prompts
will be very similar
to the Temperature
prompts.
The menus will
prompt the user for
density values and
density units.