23
LDB-ST1LE Batcher
SETUP FLOW INPUT
EXCITATION VOLTAGE
5v 12v 24v
PULSE INPUT TYPE
chA
chA=chB
Qx1 Qx2
PULSE TRIGGER LEVEL
10mV 100mV 2.5V
LOW PASS FILTER
40Hz 3KHz 20KHz
INPUT TERMINATION
Pullup Pulldown None
MAX WINDOW (1-99)
1
K_FACTOR TYPE
Avg LinTbl
AVERAGE KA-FACTOR
####### P/gal
LINEAR TABLE KA
Fre01:######## Hz
LINEAR TABLE KA
KA--01:####### P/gal
LOW FLOW RATE ALARM
####### gal/m
HIGH FLOW RATE ALARM
####### gal/m
Advance To
SETUP PULSE OUTPUT
Press ENTER to begin setup of Flow Input.
Select the desired Excitation Voltage for your flow
sensor. Caution: Improper selection may cause damage
to sensor
Enter the desired Pulse type. See side note.
Select the desired Input Pulse
T
rigger Level.
Select the desired Low Pass Filter.
(Max. Count Speed). Use 3kHz with turbine flowmeters.
Select the proper input termination.
Enter the desired Maximum Sample Window Time (1-99
sec) that can occur at the lowest flowrate. Use 1 second
for turbine flowmeters.
Enter the desired K-Factor Type.
If Avg selected, Enter the desired Average K-Factor in
the units requested.
If LinTbl selected,
Enter the desired frequency/ K-Factor pair for each point
in the Linearization Table.
NOTE: Enter 0 for Fre value of any point (other than
Fre01) to exit the routine and use the values
entered up to that point.
Enter the desired volumetric Low Rate Alarm.
This will trigger an alarm message if alarm conditions
occur. The relays are not affected.
Enter the desired volumetric High Rate Alarm.
This will trigger an alarm message if alarm conditions
occur. The relays are not affected.
6.4.5
SETUP
FLOW INPUT
(Pulse - chA &
chA=chB)
NOTE:
chA = Single Pulse
chA=chB = Pulse
checking
for missing
pulses
Qx1 = Quadrature
Qx2 = Quadrature x 2
Notes
Display
Sub-menus
Through 16 Points