SAFETY INTERLOCK ACCESS CONTROL SYSTEM

8

 

SYSTEM OPERATION

5-1. 

Wire 120VAC to internal power supply blue wire (neutral) black wire (live). Power supply should be wired to  

 

TB6 on PCB-EG001. Verify that the red ‘PWR’ LED located on PCB-EG001 is illuminated. This should remain on  

 

while power is supplied to PCB-EG001.

5-2. 

Turn the key to the ‘ON’ position, verify that the ‘POWER ON’, ‘SYSTEM READY’, and ‘ENTRYWAY CLOSED’  

 

LEDs on the control panel are illuminated. If they are not, check the jumpers located on the safety loop inputs  

 

on PCB-EG001 (TB5, 7, 8, 9, 10). Also, check to make sure all interlocked doors are closed, all emergency stop  

 

and access buttons are not depressed, and any auxiliary inputs are in the N/C state. The ‘SAFE’ LED by TB1 on  

 

PCB-EG001 should also be on as well as the ‘KEY ON’ LED on PCB-EG-MPI.

5-3.    With the start key in the ‘ON’ position; the ‘POWER ON’, ‘SYSTEM READY’, and ‘ENTRYWAY CLOSED’ LEDs on  
 

the control panel should all be illuminated. Inside the control panel the ‘SAFE’ LED adjacent to TB1 on 

 

PCB-EG001 and the ‘KEY ON’ LED on PCB-EG-MPI should be illuminated. 

5-4. 

Press the ‘START’ button; both the ‘START’ LED and the ‘MAGLOCK ON’ LED should illuminate on the control 

 

panel. Inside the control panel the ‘ENGAGED’ LED and ‘DNGR’ (danger) status LED adjacent to TB1 should be  

 

illuminated. The ‘SAFE’ LED adjacent to TB1 should not be illuminated. 

5-5.  

Press the ‘EXIT’ button; the ’EXIT’ LED should stay on and an audible signal should sound for the duration of  

 

the adjustable time period. On PCB-EG001, the ‘DNGR’ and ‘EXIT’ LEDs adjacent to TB1 and the ‘CHIME’ LED  

 

on PCB-EG-MPI should remain on for the entire exit delay period. You can now silence the audible sound by 

 

removing JP1 on PCB-EG-MPI.

5-6. 

 To set the exit duration for enter/exit periods use the ‘EXIT DURATION’ potentiometer (R14) located on 

 

PCB-EG001. Turn counter clockwise for the minimum setting of 5 seconds and clockwise for the maximum  

 

setting of 120 seconds. Press the ’ EXIT’ button to verify time settings. To reset the time when the door is  

 

closed, leave (JP9) jumper installed on PCB-EG001. If full duration is required, remove (JP9) from the PCB- 

 

EG001. Check any external switches request to exit/enter switches (optional) along with any keypads 

 

(optional) to verify the circuit is receiving input signals. 

5-7.  

Press the ‘EMERGENCY STOP’ button. Verify that the ‘MAGLOCK ON’, ‘SYSTEM READY’ and ‘START’ LEDs on  

 

the control panel turn off. Turn switch clockwise to reset. Press the ‘START’ button to reset the system and 

 

continue to test any external E-stop (optional) or E-stop access switches (optional). External emergency  

 

switches can be wired in series or connected to either TB9 or TB10 located on ETG-EG001.

5-8. The 

‘ENTRYWAY CLOSED’ LED on the control panel is used to give the status of all door safety interlock 

 

connections. Normally closed safety interlocks should be used on all entry ways to allow the Entry-Guard™ 

 

to monitor door status. These interlocks can be wired in series or connected directly to TB5 or TB7 located  

 

on PCB-EG001. Verify that when the all doors are closed, the ‘ENTRYWAY CLOSED’ LED is illuminated, and   

 

when the door is open, the ‘ENTRYWAY CLOSED’ LED is not illuminated. This safety loop will be bypassed  

 

once the ‘EXIT’ button is pressed to allow room entry or exit for selected time duration.

NOTES

5-9.  

‘POWER ON’ LED shows the key switch is on and power is applied.

5-10.  ‘MAGLOCK ON’ LED shows the status of the magnetic lock outputs.
5-11.  ‘SYSTEM READY’ LED shows when the entryway doors are all closed and all E-stops and E-access switches are 
 

not pressed.

5-12.  ‘ENTRYWAY CLOSED’ LED shows when the entryway doors are all closed.
5-13.  ‘START’ LED shows when the safety circuit is engaged.
5-14.  ‘EXIT’ LED shows when the system is in exit now mode.
5-15.  Pressing the ‘STOP’ button or turning the key switch off will turn off the Entry-Guard™ system. 
5-16.  ‘EMERGENCY STOP’ button will create a fail-safe status that will shut down laser emission completely or 
 

contain the laser beam within a laser shutter device. Once the button is pressed, it must be turned clockwise  

 

to reset. When the system has been reset, the ‘START’ button must be pressed to allow laser operation.

5  

.

Содержание Entry-Guard

Страница 1: ...OPERATION MANUAL SAFETY INTERLOCK ACCESS CONTROL SYSTEM...

Страница 2: ...PCB EG001 13 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT 14 10 5 PRINTED CIRCUIT BOARD PCB EG MPI 15 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT 16 10 7 REMOTE START WIRING 17 10 8 ACCESS CONTROL WI...

Страница 3: ...yway doors Biometric scanners PLC circuits Electronic latches Kentek s versatile system enables placement of safeguards around all possible hazards within the work environment We provide 11 outputs th...

Страница 4: ...1 DPDT normally open normally closed dry contacts 12VDC can be added by applying jumper JP1 Inductive or resistive loads surge protected to 31VDC Sign Operation Signals Safe Danger Safe Exit Now On 1...

Страница 5: ...onent outline on paper or hold the product firmly against the wall and mark the hole locations prior to mounting equipment 4 4 We recommend mounting the lowest point of the control panel between 48 56...

Страница 6: ...0 Any door to the protected room is opened without first pressing an Exit Enter request keypad or biometric scanner 4 31 The building fire alarm actuates special requirement 4 32 Power outage with no...

Страница 7: ...CESS buttons are pressed 4 54 With the SYSTEM READY LED not illuminated pressing the front panel START button does not engage the system 4 55 With the SYSTEM READY LED illuminated pressing the front p...

Страница 8: ...o reset the time when the door is closed leave JP9 jumper installed on PCB EG001 If full duration is required remove JP9 from the PCB EG001 Check any external switches request to exit enter switches o...

Страница 9: ...emergency access switches individually Press the START button to engage the system and make sure it drops to the fail safe state after each E stop request System will have to be engaged before each te...

Страница 10: ...receptacle 7 28 ETG X2 Single interlock connector plug 7 29 ETG X3 Triple interlock receptacle 7 30 ETG X4 Quad interlock receptacle Call for updated lists SPARE PARTS LIST 8 1 F 2 250 Fuse F1 8 2 RY...

Страница 11: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 11 Section 10 1 APPLICATION LAYOUT OPTIONS...

Страница 12: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 12 Section 10 2 CONTROL PANEL FACEPLATE...

Страница 13: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 13 Section 10 3 PRINTED CIRCUIT BOARD PCB EG001...

Страница 14: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 14 Section 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT...

Страница 15: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 15 Section 10 5 PRINTED CIRCUIT BOARD PCB EG MPI...

Страница 16: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 16 Section 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT...

Страница 17: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 17 Section 10 7 REMOTE START WIRING...

Страница 18: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 18 Section 10 8 ACCESS CONTROL WIRING...

Страница 19: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 19 Section 10 9 EMERGENCY ACCESS WIRING...

Страница 20: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 20 Section 10 10 EMERGENCY STOP WIRING...

Страница 21: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 21 Section 10 11 DOOR INTERLOCK WIRING...

Страница 22: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 22 Section 10 12 KEYPAD WIRING...

Страница 23: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 23 Section 10 13 MAGNETIC LOCK WIRING...

Страница 24: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 24 Section 10 14 SINGLE STATUS SIGN WIRING...

Страница 25: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 25 Section 10 15 DUAL STATUS SIGN WIRING...

Страница 26: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 26 Section 10 16 TRIPLE STATUS SIGN WIRING...

Страница 27: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 27 Section 10 17 PCB SIGN WIRING...

Страница 28: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 28 Section 10 18 BYPASS KEY SWITCH WIRING...

Страница 29: ...www kenteklaserstore com Kentek Corporation All rights reserved ENTRY GUARD is a registered trademark of Kentek Corporation...