SAFETY INTERLOCK ACCESS CONTROL SYSTEM
6
4-11. All interlocked (protected) equipment is enabled.
4-12. The ‘LASER ON’ sign is illuminated.
4-13. The ‘LASER OFF’ sign is not illuminated.
4-14. The ‘ENTER CAUTION’ or ‘EXIT NOW’sign(s) (if so equipped) should be off except during ‘EXIT NOW’ mode.
4-15. The ‘EXIT NOW’ audible alarm should not sound, except during ‘EXIT NOW’ mode.
The system is considered disengaged or in safe mode when all of the following conditions are met:
4-16. The ‘START’ LED is not illuminated.
4-17. The ‘MAGLOCK ON’ LED is not illuminated.
4-18. All doors to the protected room are unlocked (if equipped with magnetic or electronic locks).
4-19. All interlocked (protected) equipment is disabled.
4-20. The ‘LASER ON’ sign is not illuminated.
4-21. The ‘LASER OFF’ sign is illuminated.
4-22. The ‘ENTER CAUTION’ or ‘EXIT NOW’ sign(s) (if so equipped) are not illuminated.
4-23. The building security system resumes control of the door locks (special requirement).
To engage the system:
4-24. Ensure the ‘KEY SWITCH’ is on.
4-25. Ensure the ‘POWER ON’ LED is on.
4-26. Ensure the ‘ENTRYWAY CLOSED’ LED is on.
4-27. Ensure the ‘SYSTEM READY’ LED is on.
4-28. Press the ‘START’ button and the system should engage.
The system should disengage when any of the following actions are performed:
4-29. Any ‘EMERGENCY STOP’ or ‘EMERGENCY ACCESS’ button is pressed.
4-30. Any door to the protected room is opened without first pressing an Exit/Enter request, keypad or
biometric scanner.
4-31. The building fire alarm actuates (special requirement).
4-32. Power outage with no battery backup.
The system is considered to be in exit now mode when the system is engaged and the exit now circuit is activated.
The following occurs during exit now mode:
4-33. The front panel ‘EXIT’ LED illuminates.
4-34. The ‘MAGLOCK ON’ LED is NOT illuminated.
4-35. The magnetic door locks release (go to the unlocked position if equipped).
4-36. The ‘ENTER CAUTION’ and ‘EXIT NOW’ signs illuminate (if equipped).
4-37. The ‘LASER ON’ sign remains illuminated.
4-38. The ‘LASER OFF’ sign is NOT illuminated.
4-39. The audible chime sounds for 5 to 120 seconds (end user set).
4-40. While the chime is sounding, the protected doors can be opened without the system disengaging.
4-41. If the ‘EXIT NOW AUTO RESET’ jumper is in place, closing all open doors after any door was opened
terminates the exit now sequence as follows:
a. The chime signal is silenced.
b. The ‘ENTER CAUTION’ and ‘EXIT NOW’ signs turn off (if equipped).
c. The ‘MAGLOCK ON’ LED illuminates.
d. The magnetic door locks engage (go to the locked position if equipped)
e. The system remains engaged.
4-42. If the ‘EXIT NOW AUTO RESET’ jumper is not in place, closing the doors does not terminate exit now mode
before the timer times out; it will operate throughout the entire cycle.
4-43. If any door remains open when the exit now mode times out, the system reverts to disengaged mode.
Содержание Entry-Guard
Страница 1: ...OPERATION MANUAL SAFETY INTERLOCK ACCESS CONTROL SYSTEM...
Страница 11: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 11 Section 10 1 APPLICATION LAYOUT OPTIONS...
Страница 12: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 12 Section 10 2 CONTROL PANEL FACEPLATE...
Страница 13: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 13 Section 10 3 PRINTED CIRCUIT BOARD PCB EG001...
Страница 14: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 14 Section 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT...
Страница 15: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 15 Section 10 5 PRINTED CIRCUIT BOARD PCB EG MPI...
Страница 16: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 16 Section 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT...
Страница 17: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 17 Section 10 7 REMOTE START WIRING...
Страница 18: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 18 Section 10 8 ACCESS CONTROL WIRING...
Страница 19: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 19 Section 10 9 EMERGENCY ACCESS WIRING...
Страница 20: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 20 Section 10 10 EMERGENCY STOP WIRING...
Страница 21: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 21 Section 10 11 DOOR INTERLOCK WIRING...
Страница 22: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 22 Section 10 12 KEYPAD WIRING...
Страница 23: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 23 Section 10 13 MAGNETIC LOCK WIRING...
Страница 24: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 24 Section 10 14 SINGLE STATUS SIGN WIRING...
Страница 25: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 25 Section 10 15 DUAL STATUS SIGN WIRING...
Страница 26: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 26 Section 10 16 TRIPLE STATUS SIGN WIRING...
Страница 27: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 27 Section 10 17 PCB SIGN WIRING...
Страница 28: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 28 Section 10 18 BYPASS KEY SWITCH WIRING...