SAFETY INTERLOCK ACCESS CONTROL SYSTEM

3

 INTRODUCTION

Entry-Guard™ is a Safety Interlock System (SIS) that provides a fail-safe Access Control System (ACS) with a primary 
function to ensure that unauthorized personnel are prohibited from areas where laser radiation may be present. When 
the power to the controller is interrupted, critical outputs, such as door magnetic locks and laser interlocks, revert to a 
safe state: magnetic locks off, laser interlocks open. 

The SIS has become more critical recently in light of accidents in the laser industry. These incidents have led organiza-
tions to develop better operating procedures and standards that suggest a separate system be implemented for safety 
functions, away from the basic process control procedure. This separation has become an industry standard. 

  

OVERALL CONCEPT

Entry-Guard™ has the capability to integrate with components of any ACS, which may include any or all of the 
following components:

Lasers warning signs 

Safety interlocks 

Emergency stop switches

Laser shutters 

Active status lights 

Proximity sensors 

Remote start switches 

Enclosures   

Audible signals 

Safety mats 

Exit request switches 

 

Curtain systems 

Keypads 

Crash bar sensors 

Bypass key switches

Light curtains 

Card readers 

Laser scanners 

Magnetic locks 

Entryway doors 

Biometric scanners 

PLC circuits 

Electronic latches 

Kentek’s versatile system enables placement of safeguards around all possible hazards within the work environment. 
We provide 11 outputs that can be used for a wide variety of applications.

Four laser interlocks (TB13, TB14, TB15 and TB16) are double pole double throw normally open/normally closed, dry 
contacts. 12VDC can be added by applying jumpers JP10-JP13. 
 
Three auxiliary interlocks (TB17, TB18, TB19) are single pole single throw normally open, dry contacts. 12VDC can be 
added by applying jumpers JP14-JP16.

All 7 interlocks can be used to control anything that needs to be turned on or off depending on the status of the 
system. For applications that require a higher voltage or current rating, external relays can be used to switch power for 
these devices.

Two magnetic lock terminals (TB3, TB4) are double pole double throw normally open/normally closed contacts and 
can provide 12VDC (with jumpers installed JP2/JP3). Removing these jumpers individually turns each set of contacts 
to dry contacts. These contacts are bypassed while the ‘EXIT NOW’ circuit is active allowing entry into the room.

One ‘Exit now’ terminal (TB2) is double pole double throw normally open/normally closed contacts and can provide 
12VDC (with jumper installed JP1). These contacts switch during any ‘EXIT NOW’ request and remain active until the 
‘EXIT NOW’ timer is finished.

One user +12VDC terminal (TBDC) has two connections for 12VDC and ground.

1

.

2  

.

Содержание Entry-Guard

Страница 1: ...OPERATION MANUAL SAFETY INTERLOCK ACCESS CONTROL SYSTEM...

Страница 2: ...PCB EG001 13 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT 14 10 5 PRINTED CIRCUIT BOARD PCB EG MPI 15 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT 16 10 7 REMOTE START WIRING 17 10 8 ACCESS CONTROL WI...

Страница 3: ...yway doors Biometric scanners PLC circuits Electronic latches Kentek s versatile system enables placement of safeguards around all possible hazards within the work environment We provide 11 outputs th...

Страница 4: ...1 DPDT normally open normally closed dry contacts 12VDC can be added by applying jumper JP1 Inductive or resistive loads surge protected to 31VDC Sign Operation Signals Safe Danger Safe Exit Now On 1...

Страница 5: ...onent outline on paper or hold the product firmly against the wall and mark the hole locations prior to mounting equipment 4 4 We recommend mounting the lowest point of the control panel between 48 56...

Страница 6: ...0 Any door to the protected room is opened without first pressing an Exit Enter request keypad or biometric scanner 4 31 The building fire alarm actuates special requirement 4 32 Power outage with no...

Страница 7: ...CESS buttons are pressed 4 54 With the SYSTEM READY LED not illuminated pressing the front panel START button does not engage the system 4 55 With the SYSTEM READY LED illuminated pressing the front p...

Страница 8: ...o reset the time when the door is closed leave JP9 jumper installed on PCB EG001 If full duration is required remove JP9 from the PCB EG001 Check any external switches request to exit enter switches o...

Страница 9: ...emergency access switches individually Press the START button to engage the system and make sure it drops to the fail safe state after each E stop request System will have to be engaged before each te...

Страница 10: ...receptacle 7 28 ETG X2 Single interlock connector plug 7 29 ETG X3 Triple interlock receptacle 7 30 ETG X4 Quad interlock receptacle Call for updated lists SPARE PARTS LIST 8 1 F 2 250 Fuse F1 8 2 RY...

Страница 11: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 11 Section 10 1 APPLICATION LAYOUT OPTIONS...

Страница 12: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 12 Section 10 2 CONTROL PANEL FACEPLATE...

Страница 13: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 13 Section 10 3 PRINTED CIRCUIT BOARD PCB EG001...

Страница 14: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 14 Section 10 4 PRINTED CIRCUIT BOARD PCB EG001 LAYOUT...

Страница 15: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 15 Section 10 5 PRINTED CIRCUIT BOARD PCB EG MPI...

Страница 16: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 16 Section 10 6 PRINTED CIRCUIT BOARD PCB EG MPI LAYOUT...

Страница 17: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 17 Section 10 7 REMOTE START WIRING...

Страница 18: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 18 Section 10 8 ACCESS CONTROL WIRING...

Страница 19: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 19 Section 10 9 EMERGENCY ACCESS WIRING...

Страница 20: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 20 Section 10 10 EMERGENCY STOP WIRING...

Страница 21: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 21 Section 10 11 DOOR INTERLOCK WIRING...

Страница 22: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 22 Section 10 12 KEYPAD WIRING...

Страница 23: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 23 Section 10 13 MAGNETIC LOCK WIRING...

Страница 24: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 24 Section 10 14 SINGLE STATUS SIGN WIRING...

Страница 25: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 25 Section 10 15 DUAL STATUS SIGN WIRING...

Страница 26: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 26 Section 10 16 TRIPLE STATUS SIGN WIRING...

Страница 27: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 27 Section 10 17 PCB SIGN WIRING...

Страница 28: ...SAFETY INTERLOCK ACCESS CONTROL SYSTEM 28 Section 10 18 BYPASS KEY SWITCH WIRING...

Страница 29: ...www kenteklaserstore com Kentek Corporation All rights reserved ENTRY GUARD is a registered trademark of Kentek Corporation...

Отзывы: