background image

TECH SHEET - DO NOT DISCARD

PAGE 11

FOR SERVICE TECHNICIAN'S USE ONLY

PART NO. 3954702 REV. A

Pin T

Pin P

Pin V

Locking tab for

pressure switch.

Push in here and

rotate switch to

remove switch.

Figure 7

Press START.

After the tub fills, press STOP/CANCEL once.

NOTE:  Ensure proper hose connections and

household's hot water presence.

Measure the water temperature. At the WARM

setting, a temperature range of 90° - 110° F indicates

proper operation.

If the temperature is not within this range, check the

Automatic Temperature Control sensor as follows:

Remove connector P13 from the control board.

Measure the resistance between P13-7 and P13-8 at

the wire harness connector. The resistance should be

between 74 k

and 24 k

.

If resistance is not within this range, check for

continuity between the connector and sensor. If

continuity is good, replace the log valve assembly.

If fill valves and temperature sensor are functioning

properly, replace the machine control board.

TEST #6

Operating and Flood Pressure Switch

Test

Check the hose connections between each pressure

switch in the console and the pressure dome attached

to the tub.

If hose connections are good, check the Operating

Pressure Switch as follows:

Press HEAVY DUTY then START to start a cycle. Let

the unit fill and see if the operating pressure switch

turns off the water.

Check the voltage across pins P and V of the

Operating Pressure Switch. If 12 VDC is present, the

water level pressure has opened the switch. See

Figure 7.

If no voltage is present and the water has filled the

tub to a visible level (above the nutate plate), stop the

cycle and replace the Operating Pressure Switch.

To check the Flood Pressure Switch:

IMPORTANT – PERFORM THE FOLLOWING STEPS

IN THIS ORDER:

Pull the hose off of the Operating Pressure Switch so

that the washer can fill beyond the Operating Switch

trip point.

Press HEAVY DUTY then START to start a cycle. Let

the unit fill and see if Flood Pressure Switch will trip.

Check the voltage across pins P and V of the Flood

Pressure Switch. If 120 VAC is present, the water level

pressure has opened the switch. This should also

shut off the water inlet valves and give an FL

indication on the 7-segment display.

If no voltage is present and the water has filled the

tub to an over fill level, stop the cycle and replace the

Flood Pressure Switch.

Reconnect the pressure switch hoses and drain out

the water by starting an EXTENDED SPIN cycle.

TEST #7

Drain/Recirculation Test

Perform the following checks if unit fails to drain or

recirculate.

Check power to the unit per Test #1.

Refer to Test #3 and check the pump connection (P5) to

the motor controller.

Check pump motor windings by removing connector P5

from the motor controller board. Check for resistance

values shown in Table 7.

TABLE 7

WINDING

RESISTANCE CONTACTS MEASURED

RECIRCULATE to NEU

11.1 Ohms P5-3 (RD/BU) P5-1 (WH)

DRAIN to NEU

11.1 Ohms

P5-2 (TN/YL) P5-1 (WH)

RECIRCULATE to DRAIN 22.2 Ohms P5-3 (RD/BU) P5-2 (TN/YL)

If the winding measurements are much higher (tens of

Ohms to infinity) than shown in Table 7, a problem exists

in the motor winding or in the connection between the

control board and the motor. Check the resistance at the

pump motor. Remove the connector at the motor, and

take measurements as shown in Table 8.

TABLE 8

WINDING

RESISTANCE CONTACTS MEASURED

RECIRCULATE to NEU

11.1 Ohms

RD

WH

DRAIN to NEU

11.1 Ohms

YL

WH

RECIRCULATE to DRAIN

22.2 Ohms

RD

YL

If the winding measurements are much higher (tens of

Ohms to infinity) than shown in Table 8, replace the

pump motor.

If the resistance at the pump motor is correct, there is an

open circuit in the wiring between the motor and control

board. Repair or replace the lower wiring harness.

If pump motor windings and motor control board check

OK, repair or replace the pump. Be sure to check the

pump and tub sump for foreign objects before replacing

pump.

Содержание Elite 110.2108200

Страница 1: ... an anti static wrist strap Connect wrist strap to green ground connection point or unpainted metal in the appliance OR Touch your finger repeatedly to a green ground connection point or unpainted metal in the appliance Before removing the part from its package touch the anti static bag to a green ground connection point or unpainted metal in the appliance Avoid touching electronic parts or termin...

Страница 2: ...r the display If the motor controller detects an unrecoverable off balance condition the machine controller will shut down and display an ob for off balance The lid switch must be opened at least once before restarting the cycle if this condition occurs Opening the lid will allow the customer to view and redistribute the load Press STOP CANCEL to clear the display Sr signifies a failure of the rel...

Страница 3: ...s at any time all water valves should turn off Press EXPRESS WASH after step 2 below to start draining Press EXPRESS WASH again to turn off pump STEP PRESS TOUCHPAD DISPLAY CONTROL ACTION 1 Key Dance SET DELAY TIME END OF CYCLE SIGNAL SET DELAY TIME END OF CYCLE SIGNAL DIAGNOSTIC TEST INDICATOR The Water Inlet and Dispenser Valve Operating Pressure Switch Test is activated Key Dance must be comple...

Страница 4: ...ivated Key dance must be completed within 5 seconds to be valid 2 WASH RINSE TEMP 00 on the display 3 repeat Cold Water Inlet Valve and Fabric Softener dispenser valve on Cold Cold and Normal above WASH TIME LEDs will turn on 4 WASH TIME Normal LED will turn off and Normal Maximum LED will turn on Fabric softener valve will shut off and Fresh water valve will turn on 5 WASH RINSE TEMP Normal Maxim...

Страница 5: ...t progresses STEP DESCRIPTION OF SEQUENCE DISPLAY In Seconds INLET VALVE Hot or Cold DISPENSER WASH TIME LED LIT PUMP MOTOR ACTION DRIVE MOTOR ACTION DRIVE MOTOR SPEED 1 NUTATE FILL 99 81 COLD FRESH MAX NORM OFF NUTATE 300 2 NUTATE RECIRCULATE 80 61 COLD FAB SOFT NORMAL RECIRCULATE NUTATE 275 3 NUTATE FILL DRAIN 60 41 BOTH BLEACH NORM MIN DRAIN NUTATE 250 4 NUTATE FILL DRAIN 40 21 HOT DETERGENT MI...

Страница 6: ...RLAY TOUCH SCREEN LED ASSEMBLY FRESH VALVE ATC SENSOR P13 P11 2 1 2 8 7 3 5 4 6 TN OR BU OR OR BK WH OR FABRIC SOFTENER VALVE BLEACH VALVE DETERGENT VALVE 3 2 1 OPERATING PRESSURE SWITCH LID SWITCH 3 4 5 TN VT OR 3 2 1 GY WH WH RD T P11 P12 MACHINE CONTROL LOG VALVE BK WH GY GY PK FLOOD PRESSURE SWITCH BU 1 PK 4 3 2 1 P16 3 4 5 2 1 1 2 3 P6 2 3 4 5 RD SHIELD WH BK 1 YL WH RD WH RD BU TN YL WH BU B...

Страница 7: ...m an over fill could indicate a failure to drain WON T NUTATE AT ANY SPEED 1 Check harness connections 2 Drive motor See Test 3 3 Drive mechanism failure WON T SPIN AT ANY SPEED 1 Check harness connections 2 Drive motor See Test 3 3 Drive mechanism failure MOTOR OVERHEATS 1 Drive motor See Test 3 WON T DRAIN 1 Check pump See Spin and Drain Test in Diagnostic Tests section 2 Check pump motor 3 Chec...

Страница 8: ... VAC see Troubleshooting Test 1 the control board has a faulty valve driver Replace the machine control board If the voltage measurements are correct check the individual solenoid valves Unplug the washer and disconnect connector P13 from the control board Check the resistance at contacts shown in the following Table 2 If resistance is outside of range replace the entire log valve assembly TABLE 2...

Страница 9: ...e motor controller board Check for the resistance values shown in Table 3 For ground contact use a ground screw attached to the top If the winding measurements are much higher tens of Ohms to infinity than shown in Table 3 a problem exists in the motor winding or in the connection between the control board and the motor Check the resistance at the drive motor Remove the connector at the motor and ...

Страница 10: ...by pressing the START touchpad Check for the following situations None of the LEDs light up A particular group of LEDs does not light up A single LED does not light up No beep sound is heard No washer function is activated when a particular touchpad is pressed None of the LEDs light up Visually check that connectors P11 and P12 are inserted all the way into the machine controller A particular grou...

Страница 11: ... Switch trip point Press HEAVY DUTY then START to start a cycle Let the unit fill and see if Flood Pressure Switch will trip Check the voltage across pins P and V of the Flood Pressure Switch If 120 VAC is present the water level pressure has opened the switch This should also shut off the water inlet valves and give an FL indication on the 7 segment display If no voltage is present and the water ...

Страница 12: ... both mounting screws into control board and secure to control bracket Plug all connectors into the control board Reconnect ribbon connectors so that the ribbon is wrapped around the two wire GY WH and BK WH leads Plug wire harness snap tie into top of board To remove motor control board Remove all connectors from the control board Remove lock down screw from plastic bracket mounting screw 1 see F...

Отзывы: