FIGURE 13.

Louvers and Grilles: In calculating free area, consideration
shall be given to the blocking effect of louvers, grilles or
screens protecting openings.  Screens used shall not be
smaller than 1/4 inch (6.4 mm) mesh.  If the free area through
a design of louver or grille is known, it should be used in
calculating the size opening required to provide the free area
specified.  If the design and free area is not known, it may be
assumed that wood louvers will be 20-25 percent free area
and metal louvers and grilles will have 60-75 percent free
area.  Louvers and grilles shall be fixed in the open position
or interlocked with the equipment so that they are opened
automatically during equipment operation.

Special Conditions Created by Mechanical Exhausting or
Fireplaces: operation of exhaust fans, ventilation systems,
clothes dryers or fireplaces may create conditions requiring
special attention to avoid unsatisfactory operation of installed
gas utilization equipment.

Water Piping

HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water.  Water
heated to a temperature which will satisfy space heating,
clothes washing, dish washing, cleaning and other sanitizing
needs can scald and permanently injure you upon contact.
Some people are more likely to be permanently injured by
hot water than others.  These include the elderly, children,
the infirm, or physically/mentally handicapped.  If anyone using
hot water in your home fits into one of these groups or if there
is a local code or state law requiring a certain temperature
water at the hot water tap, then you must take special
precautions.  In addition to using the lowest possible
temperature setting that satisfies your hot water needs, a

means such as a *mixing valve, shall be used at the hot water
taps used by these people or at the water heater. Mixing valves
are available at plumbing supply or hardware stores, see
Figure 14 below. Valves for reducing point of use temperature
by mixing cold and hot water are also available. Follow
manufacturer’s instructions for installation of the valves.
Before changing the factory setting on the thermostat, read
the 

Temperature Regulation

 section in this manual.

            

FIGURE 14.

This water heater shall not be connected to any heating systems
or component(s) used with a non-potable water heating
appliance.

All piping components connected to this unit for space heating
applications shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment shall
not be introduced into this system.

Water supply systems may, because of such events as high
line pressure, frequent cut-offs or the effects of water hammer
among others, have installed devices such as pressure reducing
valves, check valves, back flow preventers, etc. to control these
types of problems.  When these devices are not equipped with
an internal by-pass, and no other measures are taken, the
devices cause the water system to be closed.  As water is heated,
it expands (thermal expansion) and closed systems do not allow
for the expansion of heated water.

The water within the water heater tank expands as it is heated
and increases the pressure of the water system.  If the relieving
point of the water heater’s temperature-pressure relief valve is
reached, the valve will relieve the excess pressure.  

The

temperature-pressure relief valve is not intended for the
constant relief of thermal expansion.

  This is an unacceptable

condition and must be corrected. It is recommended that any
devices installed which could create a closed system have a
by-pass and/or the system have an expansion tank to relieve
the pressure built by thermal expansion in the water system.
Refer to the 

Thermal Expansion

 section under 

Troubleshooting

Guide

 or contact local plumbing authority or local Sears Service

Center on how to control this situation.

NOTE:

 

To protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.

Содержание 153.338003

Страница 1: ...EATER Safety Instruction Installation Operation Care and Maintenance Troubleshooting Parts List COMMERCIAL GAS WATER HEATER Si no puede leer o entender el inglés y necesita el manual instructivo y o etiquetas en español puede obtenerlos llamando al 1 800 821 2017 NO TRATE DE INSTALAR O OPERAR ESTE CALENTADORDEAGUAsinoentiendelainformaciónenlasetiquetas o en el manual instructivo No hacer caso de e...

Страница 2: ...llow the safety message and how to avoid the risk of injury IMPORTANT DEFINITIONS Gas Supplier The natural gas or propane utility or service who supplies gas for utilization by the gas burning appliances within this application The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the natural gas meter or propane storage tank of a buil...

Страница 3: ...3 SAFETY PRECAUTIONS ...

Страница 4: ...essure Relief Valve 13 14 Filling the Water Heater 14 Venting 15 16 Gas Piping 16 17 Sediment Trap 17 OPERATING INSTRUCTIONS 18 19 Lighting Operating Label 18 Temperature Regulation 19 SERVICE AND ADJUSTMENT 20 22 Tank Sediment Cleaning 20 Venting System Inspection 20 Burner Inspection 20 21 Burner Cleaning 21 Housekeeping 21 Anode Rod Inspection 21 Temperature Pressure Relief Valve Operation 21 2...

Страница 5: ...nderstand any portion of the instructions call the Sears Service Center Carefully plan the place where you are going to put the water heater Correct combustion vent action and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires See figures 1 and 8 through 13 Examine the location to ensure the water heater complies with the Facts to Consid...

Страница 6: ...28 711 mm DIAMETER FOR WATER HEATERS HAVING A DIAMETER 26 660 mm OR LESS Basic Tools You may or may not need all these tools depending on your type of installation These tools can be purchased at your local Sears Store Pipe Wrenches 2 14 356 mm Screwdriver Tin Snips 6 1 82 m Tape or Folding Ruler Garden Hose Drill Pipe Dope or Teflon Tape Additional Tools Needed When Sweat Soldering Tubing Cutters...

Страница 7: ...Joint Union J Drip Leg Sediment Trap K Inner Door L Outer door M Union N Inlet Water Shut off Valve O Cold Water Inlet P Inlet Dip Tube Q Temperature Pressure Relief Valve R Rating Plate S Flue Baffle s T Thermostat U Drain Valve V Pilot and Main Burner W Flue X Drain Pan V PILOT MAIN BURNER ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATION ON ROOF T THERMOSTAT CLOSED WATER SYST...

Страница 8: ...he vent pipe can be lifted off after any screw or other attached devices are removed Dispose of the draft hood The new water heater has a draft hood which must be used for proper operation 6 If you have copper piping to the water heater the two copper water pipes can be cut with a hacksaw approximately four inches away from where they connect to the water heater see Figure 6 This will avoid cuttin...

Страница 9: ... can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the dr...

Страница 10: ...cleaning establishments or self service laundries with dry cleaning equipment it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas Propellants of aerosol sprays and volatile compounds cleaners chlorine based chemicals refrigerants etc in addition to being highly flammable in many cases will also change to corr...

Страница 11: ...es meets the criteria for an unconfined space The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination Each opening shall have a minimum free area of one square inch per 1 000 Btu per hour 22 cm2 kW of the total input rating of all gas utilization equipment in the confined space but not less than 100 square inches 645 cm2 One...

Страница 12: ...or reducing point of use temperature by mixing cold and hot water are also available Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual FIGURE 14 This water heater shall not be connected to any heating systems or component s used with a non potable water heating appliance All...

Страница 13: ...ied combination temperature pressure relief valve by the manufacturer The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves andAutomatic Gas Shut off Devices for Hot Water Supply Systems ANSI Z21 22 and the code requirements of ASME If replaced the valve mu...

Страница 14: ...et of the temperature pressure relief valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating the valve it fails to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperat...

Страница 15: ...ystem which terminates to the outdoors Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation For proper draft hood attachment the draft hood legs may be angled slightly inward Place the draft hood legs in the receiving holes on the top of the water heater The legs will snap in the holes to give ...

Страница 16: ... line serving the water heater and A drip leg sediment trap ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit Be sure to check all the gas piping for leaks before lighting the water heater Use a soapy water solutio...

Страница 17: ... fire or explosion Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a drip leg sometimes called a sediment trap must be incorporated in the piping The drip leg must be readily accessible Install in accordance with the Gas Piping section Refer to the current edition of the National Fuel Gas Code ANSI Z223 1 NF...

Страница 18: ...wise until it stops 3 Push the gas control knob down slightly and turn clockwise to OFF see Figure A NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed down slightly Do not force 4 Remove the inner and outer burner doors located below and behind the gas control unit 5 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on thi...

Страница 19: ...7 8 C FIGURE 22 Temperature Regulation Due to the nature of the typical gas water heater the water temperature in certain situations may vary up to 30 F 16 7 C higher or lower at the point of use such as bathtubs showers sink etc Any water heater s intended purpose is to heat water Hot water is needed for cleansing cleaning and sanitizing bodies dishes clothing Untempered hot water can present a s...

Страница 20: ... of this manual Vent System Inspection At least once a year a visual inspection should be made of the venting system You should look for Obstructions which could cause improper venting The combustion and ventilation air flow must not be obstructed Damage or deterioration which could cause improper venting or leakage of combustion products Rusted flakes around top of water heater Be sure the vent p...

Страница 21: ...uld catch on fire Anode Rod Inspection The anode rod is used to protect the tank from corrosion Most hot water tanks are equipped with an anode rod The submerged rod deteriorates to protect the tank Instead of corroding the tank water ions attack and eat away the anode rod This does not affect the water s taste or color The rod must be maintained to keep the tank in operating condition Anode deter...

Страница 22: ...ndition persists or you are uncertain about the operation of the water heater let the Sears Service Center check it out Contact Sears Service Center at 1 800 4 MY HOME 1 800 469 4663 If after manually operating the valve it fails to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature...

Страница 23: ...er for assistance in controlling these situations see Figure 26 and Figure 26 A FIGURE 26 FIGURE 26A Thermal Expansion Tank Specifications Tank Dimensions Pipe Model Capacity in Inches Fitting Number In Gallons Diameter Length On Tank 153 331050 5 11 279 mm 14 3 4 375 mm 3 4 Male NOTE Expansion tanks are pre charged with a 40 psi air charge If the inlet water pressure is higher than 40 psi the exp...

Страница 24: ...rogen sulfide gas dissolved in the water The smell is the result of four factors which must all be present for the odor to develop a concentration of sulfate in the supply water little or no dissolved oxygen in the water a sulfate reducing bacteria within the water heater This harmless bacteria is non toxic to humans an excess of active hydrogen in the tank This is caused by the corrosion protecti...

Страница 25: ... pressure relief valve may be leaking at the tank fitting F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Combustion products contain water vapor which can condense on the cooler surfaces of the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and...

Страница 26: ...pilot burner Clean pilot assembly Thermocouple malfunction Replace pilot assembly and or thermocouple Thermocouple tip is not in contact with pilot flame Insert thermocouple correctly Defective Gas Control Replace Gas Control Heater not lit or thermostat not on Refer to LIGHTING INSTRUCTIONS Thermostat set too low Refer to TEMPERATURE REGULATION Heater undersized Reduce hot water use Low gas press...

Страница 27: ... Anode Rod 9004092 9004097 2 Burner Head 9006200 9006200 3 Burner Orifice 9003732 9003732 4 Burner Tube 9006199 9006198 5 Cleanout Cover 9004098 9004098 6 Cleanout Gasket 9004099 9004099 7 Cleanout Jacket cover 9003900 9003900 8 Cleanout Screw 9004100 9004100 9 Draft Hood 9003737 9003737 10 Draft Hood Bracket 9003738 9003738 11 Drain Valve 9003907 9003907 12 Flue Baffle 9003736 9006202 14 Gas Cont...

Страница 28: ... preventive maintenance or repair from time to time That s when having a Master Protection Agreement can save you money and aggravation Purchase a Master Protection Agreement now and protect yourself from unexpected hassle and expense The Master Protection Agreement also helps extend the life of your new product Here s what s included in the Agreement Expert Service by our 12 000 professional repa...

Отзывы: