Technische Eigenschaften
DN
Throughflow (l/
min.) Qmin - Qmax
Frequency (f)
Portable device
range
10
0,9 - 15
ca. 30...388 Hz
>a<
15
1,8 - 32
ca. 24...385 Hz
>b<
20
3,5 - 50
ca. 21...279 Hz
>c<
25
5,0 - 85
ca. 14...233 Hz
>d<
32
9,0 - 150
ca. 13...206 Hz
>e<
40
11,0 - 188
ca. 15...264 Hz
>f<
50
18 ,0- 316
ca. 11...191 Hz
>g<
Example:
shell code
>c<
For unequivocal identification of the sensor’s attendant measuring ranges, each sensor
dimension on the protective cap of the upper shell is supplied with the relevant letter
(e.g. >c<),
in order to avoid erroneous settings in the central building control system or the optio-
nal portable measuring device (Figure 138 00 002).
Example: shell code >c< indicates a DN 20 sensor size (or valve size) with a measurable through
-
flow of 3.5 – 50 l/min. and a frequency f of ca. 21…279 Hz.
Throughflow Measurement (Figure 138 4G): Measuring range for water
Throughflow Measurement (Figure 138 6G): Measuring range for water:
1.2
1.2
Throughflow Q / Power I
out of the
measuring range
Throughflow in %