14  roof installation – evacuated tube collectors  

Kelvinator solar hot water systems

Roof installation –  

evacuated tube collectors

Fix the bottom straps into the roof struts or trusses using 
appropriate screws, making sure the bottom rail is inclining 
towards the proposed outlet end of the collectors. 
If installing on a tiled roof, place the tiles back into their 
normal positions after fixing the straps.

Preparing and fixing the collectors

Unpack each collector and check the contents against the 
components list, being sure to leave the protective plastic 
cover on each collector. This is important as the collector 
connections will become very hot once exposed to solar 
radiation and may cause a safety hazard or prevent the 
installation of the pipe work to the collectors. Carefully lift 
the collectors onto the roof and place them in position, 
resting against the bottom rail of the collector mounting kit 
already fixed to the roof. 
Before the collectors are fixed to the roof and mounting kit, 
they are to be connected together forming an array (two and 
three collector installations only). The compression union 
fittings supplied with the collectors are used to join the 
collectors together.
Place the copper sleeve supports into the manifold pipes 
of each collector. Slide the fittings onto one side of the 
manifold pipe to be joined and then push both collectors 
together. The collector manifold pipes shall be inserted as far 
as possible into both sides of the compression union fitting. 

solar collectors

copper sleeve 

support

collector  

manifold  

pipes

compression 

union

Using two spanners, tighten each nut on the compression 
union fitting one side at a time, with one spanner used to 
brace the fitting in the middle. Tighten both sides of the 
compression union fitting until the copper olives are firmly 
sealed against both collector manifold pipes.

This standard roof mounting kit is not suitable for cyclone 
prone regions. Refer to the warning in the Important Safety 
Instructions section.

Preparing the mounting kit

Unpack the collector mounting kit(s) and check that all 
components are included. 
Slide the bottom straps onto the bottom rail and join the 
bottom rails together using the rail joiner(s) if you are 
installing two or three collectors.

Adjust the straps on the bottom rail so that they are evenly 
spaced and place the bottom rail assembly on the roof in the 
installation location decided. If installing on an iron roof, line 
up the bottom straps to the existing roofing screws that are 
fixing the iron roofing membrane to the struts.

If installing on a tiled roof lift up the tiles and line up the 
bottom straps with the roof struts or trusses. 

Содержание KCT45036A

Страница 1: ...Solar Hot Water Systems Installation Manual...

Страница 2: ...d please contact your local authorities for the correct method of disposal warning Contact an authorised installer for installation of this hot water system Contact an authorised service technician fo...

Страница 3: ...insulation may be required to comply with the requirements of AS NZS 3500 4 Plastic pipe MUST NOT be used as it will not withstand the temperature and pressure of the water generated by the solar col...

Страница 4: ...copper fin with TiNOx selective coating Glazing 4mm low iron tempered patterned glass Insulation material 40mm glass wool Collector Evacuated tube KCPE12A Number of evacuated tubes per collector panel...

Страница 5: ...pump type UP15 14B Circulation pump power 25W Rated voltage of circulation pump AC 220 240V Frequency 50Hz Model number KCT27000A KCT27036A KCT34000A KCT34036A KCT45036A Diameter mm 648 648 730 Height...

Страница 6: ...the National Plumbing Standard AS NZS 3500 4 and local authority requirements Ensure the roof structure is suitable to carry the full weight of the solar collectors Each flat panel solar collector and...

Страница 7: ...implement a water pre treatment process to bring the water quality to within acceptable limits to support the installation The saturation index SI is a measure of the corrosive or scaling properties...

Страница 8: ...mm for three solar collectors If the roof material is uneven where the collectors are to be installed then it may be necessary to add an additional 10 mm to the above distances for each collector Spac...

Страница 9: ...16 1 evacuated tube collector 17 1 connector evacuated tube collector 18 2 connector sleeve support evacuated tube collector 19 2 connector to 1 2 male for evacuated tube collector Supplied in kit KK...

Страница 10: ...one for the bottom and are supplied in the mounting kit s solarcollectors collector manifold pipes compression union Slide the fittings onto one side of the collector manifold pipe to be joined and t...

Страница 11: ...Ensure the vent valve is installed so that its vent is pointing directly upwards perpendicular to the ground not the roof ventvalve 1 2 femaleto copperunion sensorpocket 1 2 maleto collectorunion 1 2...

Страница 12: ...ulations including AS3500 plumbing and drainage requirements and AS3000 electrical wiring standards Bottom rail connection viewed from above 10 15mm fromhorizontal bottomrail assembly 1 5m reliefvalve...

Страница 13: ...e with all local regulations including AS5601 gas installation requirements AS3500 plumbing and drainage requirements and AS3000 electrical wiring standards Bottom rail connection viewed from above 10...

Страница 14: ...to the manifold pipes of each collector Slide the fittings onto one side of the manifold pipe to be joined and then push both collectors together The collector manifold pipes shall be inserted as far...

Страница 15: ...top brackets to the roof strut by either using an existing roofing screw or adding a new one Fix the top brackets to each side of the collector array with the supplied self tapping screws If installin...

Страница 16: ...ealing the copper olive to the collector manifold pipes collector 1 2 male compression union Open the fittings kit KKSSURA and check that all components have been supplied see components list Since th...

Страница 17: ...Bottom rail connection viewed from above 10 15mm fromhorizontal bottomrail assembly 1 5m reliefvalve uncontrolled hotwater outlet kitchen laundry tempered 50 C hot wateroutlet bathrooms tempering valv...

Страница 18: ...umbing and drainage requirements and AS3000 electrical wiring standards Bottom rail connection viewed from above 10 15mm fromhorizontal bottomrail assembly reliefvalve uncontrolled hotwateroutlet kitc...

Страница 19: ...m mounting surface to spread its load The storage tank shall be checked with a spirit level to ensure it is level for a number of reasons to ensure the correct positioning of the anode inside the tank...

Страница 20: ...t water system under local plumbing requirements If the hot water system is installed in a bad water quality area where regular flushing is required due to sediment build up a drain cock or valve is a...

Страница 21: ...e g bathroom or ensuite fixtures The water supplying these fixtures shall not exceed 50 C as required by AS 3500 4 heat trap uncontrolled hot water outlet kitchen laundry tempered hot water outlet 50...

Страница 22: ...sensors should not be run alongside power supply cables as this may induce a false signal into the sensor cable Installing the collector array temperature sensor The collector sensor cable is provide...

Страница 23: ...ng rules the local electrical authority regulations and any other applicable standards The pipe work storage tank and collectors are to be properly connected to the earthing system of the premises in...

Страница 24: ...f the storage tank be completed first before the cable is wired to the switchboard If you are replacing an existing electric hot water system and re using the existing cable ensure that the power supp...

Страница 25: ...ing the hot water system with water and checking for leaks At this stage the power to the tank element and pump station should be isolated off Fully open the cold water isolation valve located on the...

Страница 26: ...that the temperature sensors are installed correctly connected to the solar controller and that the cables have not been damaged If the red LED is emitting continuous flashes this indicates that wate...

Страница 27: ...e the isolation valve on the inlet piping Drain the water out of the system by activating the relief valve Remove the flow sensor from the circuit and re connect the collector array piping leaving the...

Страница 28: ...with a thermometer if the water temperature in the bathroom is over 50 C if so the tempering valve may have an incorrect setting or be malfunctioning Please call a service technician Water is dischar...

Страница 29: ...Kelvinator solar hot water systems notes 29 Notes...

Страница 30: ...30 notes Kelvinator solar hot water systems Notes...

Страница 31: ...sported at the owner s cost and risk while in transit to and from Electrolux or its ASC 6 Proof of purchase is required before you can make a claim under this warranty 7 You may not make a claim under...

Страница 32: ...er information about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux c...

Отзывы: