4 Commissioning
DE
EN
FR
IT
ES
FR
The drive is tested without the coupled mechanics. The test run is con-
ducted in the speed controlled mode, independently from the selected
pre-set solution.
A test run is still possible, even if the motor has already been coupled to
the system:
1. Enable Safe Standstill
High level on terminal X2/16
2. Set power stage enable ENPO
High-level at terminal X2/12
Observe the temporal behaviour of the inputs.
* After controller initialisation as a consequence of parameter change
3. Control with D
RIVE
M
ANAGER
:
Select "speed control" and start the drive, e.g. with nominal value
100 min
-1
.
Fig. 4.8
Control
Input safe stop
Input ENPO
Start
Device status: "Loop control active"
t
≥
2 ms
4 ms ... 1 s*
ENPO
Start
≥
2 ms
Sicherer Halt Freigabe
D
RIVE
M
ANAGER
Open-loop control
or:
Active device
>
Open-loop con-
trol> Basic operating modes