Operating Instructions CDF3000
3-13
3 Installation
DE
EN
FR
IT
ES
FR
Attention:
On the usage of motors from other manufacturers, it is to be
ensured the motor temperature sensor used is adequately
isolated from the motor winding.
3.5.4 Project plan-
ning notes on
encoder con-
nection
The max. lines per revolution of the encoder can be calculated with the
following formula.
Example for n
max
= 6000 rpm, f
Grenz
= 150 kHz:
calculated:
Pulses/rev.
selected:
An encoder with 1024 pulses/rev.
Minimum motor speed
Formula to calculate the minimum displayable motor speed n
min
, depend-
ing on the lines per revolution of the encoder.
Note:
A speed < n
min
cannot be measured. In this range the actual
speed of 0 min
-1
is set. In the range 0 < n < n
min
the ampli-
fication of the encoder is reduced.
Measurement
voltage U
MAX
–
5 V
–
Error message
E-OTM
* During the KTX evaluation the shutdown temperature can be selected between limits (
150 °C
... 250 °C)
Table 3.7
Motor temperature monitoring specification
SZ
max
=
Maximum number of encoder lines in
pulses per rev.
n
max
=
maximum speed of motor in rpm
f
grenz
=
maximum input signal frequency of
interface
SZ
max
=
60 f
Grenz
.
n
max
SZ
max
=
60 150.000
.
6000
= 1500
SZ
=
Number of lines of encoder in pulses per rev.
n
min
=
minimum speed of motor in rpm
n
min
=
3000 .
SZ
min
1
Содержание CDF3000
Страница 1: ...Positioning controller Rated current 8 A Power supply 24 48 V DC CDF3000 Operation Manual...
Страница 12: ...Operating Instructions CDF3000...
Страница 16: ...1 4 Operating Instructions CDF3000 1 Safety...
Страница 54: ...3 34 Operating Instructions CDF3000 3 Installation...
Страница 78: ...4 24 Operating Instructions CDF3000 4 Commissioning...
Страница 84: ...5 6 Operating Instructions CDF3000 5 Troubleshooting...