General Control Card Parameters (Operator Functionality)
Id-Text
Name
Parameter index
os07
node ID
0x2087
Meaning
This parameter specifies the inverter address for the diagnostic
interface (DIN 66019). The parameter is an image of the system
parameter Sy06.
Type
Variable
Data length
8 bit
Access
read / write
Coding
0...239
Standard value: 1
Note
-
Id-Text
Name
Parameter index
os08
operator type
0x2088
Meaning
Displays the implemented control card functions.
Type
Variable
Data length
16 bit
Access
read
Coding
Bit 0
Initiator
0: without
1: with initiator
Bit1
Keyboard/display
0: without
1: with keyboard/LC display
Bit 8
PU image
0: with power unit image
1: without power unit image
Bit 10
f = 0Hz
0: without
1: with f=0Hz functionality
Bit 11
STO
0: without safety function
1: with safety function STO
Bit 12...13
Bus connection
0: without (standard)
1: CANopen
2: IO-Link
3: EtherCAT
4: VARAN
Standard value: 0
Note
-