45
General Control Card Parameters (Operator Functionality)
Id-Text
Name
Parameter index
os13
operator state
0x208D
Meaning
Displays the state of the power unit, as well as the image of the
power unit parameter of the control card.
Type
Variable
Data length
8 bit
Access
read
Coding
Bit 0
reserved
Bit 1...2
PUConfIDState
0: PU-ID unknown
2: PU-ID OK
4: PU-ID incorrect
Bit 3...5
PU image state
0: PU-Image not init.
1: write PU image
3: PU-Image changed
4: PU-Image init.
5: PU-Image check
6: PU image not available
Bit 6...15
reserved
Standard value: 0
Note
-
Id-Text
Name
Parameter index
os14
store state
0x208E
Meaning
Non-volatile parameters are immediately stored by writing of
value "0". After completion of the storage the value jumps to
status "1". If at the end of the download lists in COMBIVIS the
value "0" comes before value "1", COMBIVIS will send the value
as long as the inverter has completed the storing.
Type
Variable
Data length
8 bit
Access
read / write
Coding
0: busy
1: ready
2: off
Standard value: 1
Note
-