GB - 9
Technical Data
2.
Technical Data
2.1
Operating conditions
Standard
S t a n d a r d /
class
Instructions
Definition according to
EN 61800-2
Inverter product standard:
rated specifications
EN 61800-5-1
Inverter product standard:
general safety
Site altitude
max. 2000 m above sea level
With site altitudes over 1000 m a derating of 1 % per
100 m must be taken into consideration.
Ambient conditions during operation
Climate
Temperature
EN 60721-3-3
3K3
extended to -10…45 °C
With temperature over 45°C to max. 55°C a derating of
5 % per 1 K must be taken into consideration.
Humidity
3K3
5…85 % (without condensation)
Mechanical
Vibration
Track
EN50155
max. amplitude of a vibration 1 mm (5…13 Hz)
max. acceleration amplitude 7 m/s² (13…100 Hz)
1 m/s² (100…200 Hz)
Germ. Lloyd Part 7-3
EN 60721-3-3
3M1
Contamination
Gas
3C2
Solids
3S2
Ambient conditions during transport
Climate
Temperature
EN 60721-3-2
2K3
Humidity
2K3
(without condensation)
Mechanical
Vibration
2M1
15 m/s² (200…500 Hz)
Surge
2M1
50 g/30 ms; drop from 0,25 m height
Contamination
Gas
2C2
Solids
2S2
Ambient conditions for the storage
Climate
Temperature
EN 60721-3-1
1K4
Humidity
1K3
(without condensation)
Contamination
Gas
1C2
Solids
1S2
Type of protection
EN 60529
IP20
Environment
IEC 664-1
Pollution degree 2
Definition according to
EN 61800-3
Inverter product standard:
EMC
EMC emitted interference
Cable-based interferences
–
C1/C2
see chapter 3.2.2.3
Radiated interferences
–
C2
Interference immunity
Static discharges
EN 61000-4-2 8 kV / 6 kV
AD (air discharge) / CD (contact discharge)
Burst - control lines + bus
EN 61000-4-4 2 kV
Burst - mains supply
EN 61000-4-4 4 kV
Surge - mains supply
EN 61000-4-5 1 kV / 2 kV
Phase-phase / phase-ground
Immunity to conducted distur-
bances, induced by radio-fre-
quency fields
EN 61000-4-6 10 V
0,15-80 MHz
Electromagnetic fields
EN 61000-4-3 10 V/m
Voltage variation /
voltage drop
EN 61000-2-1
+10 %, -15 %; 90 %
Voltage unsymmetries /
frequency changes
EN 61000-2-4
3 %; 2 %