GB - 16
Connection of the Power Unit
3.2.1.2 AC supply 400V / 3-phase
Picture 3.2.1.3
Connection of the mains supply
L1
L2
L3
PE
L1
L2
L3
U
V
W
PE
PE
T1 T2
1
Mains voltage
3-phase 400 V AC
Mains form
TN, TT
IT
Personal protection
RCMA with separator or
RCD type B
Earth leakage monitor
2
Main fuses
Type gG or MCCB
3
Mains contactor
4
Mains choke (optional)
13/14/15Z1B04-1000
5
KEB COMBIVERT
G6-C
3.2.1.3 Line terminal strip X1A
Picture 3.2.1.1
Description of the line terminal strip X1A
X1A
Name Function
Cross-section
Tightening
torque
L1, L2,
L3
Mains connection
3-phase
0.2-16 mm²
AWG 26-6
2.3 Nm
20.5 lb-inch
PE,
Connection for
shielding/
earthing
Screw M4 for
ring thimble
1.3 Nm
11 lb inch
3.2.1.4 Conductor cross-section of the power supply
Size
Recommended minimum cross section at rated power.
13
3 x 4 mm² Phase + 1 x 4 mm² PE
14
15
3 x 6 mm² Phase + 1 x 6 mm² PE