GB - 16
COMBICONTROL
4.4 Multi-function switch/button S1
The multi function switch/button is constructed as follows:
The button S1 is assigned with the following functions
Activity
Function
Stop --> Run
Program is started
Run --> Stop
Programm is stopped, all variables are resetted (reset
warm)
Stop --> Clear and hold (> 3 s)
until LD 2 lights
After releasing the switch all retain variables are resetted
(reset cold)
Stop --> Clear and hold (> 10 s)
until LD 1+2 light
All variables and the boot project are cleared (reset
origin) after releasing the button. If a memory card is
plugged-in, all files are copied from the card into the in-
ternal flash memory. Existing files (e.g. the boot project)
are overwritten.
Stop --> Clear 3 x within 2 s
All files of the internal flash are copied onto a plugged-in
memory card. Existing files are overwritten. LD2 lights
up briefly.
clear (button)
stop/reset
run (switch)