27
Note:
For installation in control cabinets and in par-
ticular, in closed containers, make sure the
recommended ambient temperature is main-
tained.
For further details please refer to section 7
Technical specifications.
Figure 19
Mounting position
3.4
Mounting position
The HMI device is suitable for installation in:
Mounting cabinets
Control cabinets
Switchboards
Consoles
3.4.1
Damage due to overheating
The operative temperature must be between 0° and 50°C.
All HMI systems are designed for vertical mounting position.
An inclined installation reduces the thermal convection by the HMI device
and the maximum permissible ambient temperature for operation. Please
contact KEB for details.
The HMI device may otherwise be damaged and its certifications and war-
ranty will be void.