background image

B. THERMOPILE OUTPUT CHECK

(“B” Reading. Thermostat contacts OPEN - Main burner
OFF.)

1. Thermopile system - 325 millivolts minimum. If the

minimum millivolt reading is not obtainable, readjust
thermopile for maximum millivolt output. If  millivolt reading
is still below minimum specified, replace thermopile.

C. THERMOSTAT RESISTANCE CHECK

(“C” Reading. Thermostat contacts CLOSED - Gas valve
knob “ON”. Main burner should be ON.)

1. If the “C” reading drops more than 80 millivolts, the

resistance in the system is excessive and must be
reduced. To correct:

a. Clean and tighten thermostat leads and connections.

b. Shorten or replace theirmostat lead wires.

c. Cycle thermostat rapidly (manually turn dial) to clean
contacts.

D. AUTOMATIC PILOT DROPOUT CHECK

1. Hold gas valve knob depressed in pilot position until

maximum output is observed. Then extinguish pilot and
observe meter.

2. Dropout of automatic pilot magnet (sound should be

audible) should occur between 75 millivolts and 25
millivolts. If dropout occurs outside these limits, change
the valve.

WARNING AND OPERATING PLATES

All warning and operating plates on the Keating
MIRACLEAN® Griddle should be in place at all times.
If plates are damaged or lost, replace them
immediately. 

10

SERVICE DIAGNOSIS

The following diagnosis is only to be used as a guide to qualified service personnel. Keating recommends that you use a
qualified service company. (Equipment still under warranty requires it.)

NOTE: 

To correctly and quickly diagnose the system, the chart below should be followed in sequential order.

TROUBLE SHOOTING CHART

PROBLEM

PROBABLE CAUSE

SOLUTION

No pilot

a. Quick disconnect not engaged.

a. Open gas supply valve.

b. Gas supply not “ON”.

b. Press gas valve knob in “pilot” position 

and hold.

c. Gas valve is in "OFF" position.

c. Reconnect quick disconnect.

d. Air in gas lines.

d. Turn valve knob to "pilot".

e. Faulty Piezo Ignitor.

e. Replace ignitor.

Pilot won’t stay on

a. Loose  wires.

a. Tighten connections on all wires.

b. Faulty thermopile.

b. Replace thermopile.

c. Inadequate gas supply.

c. Increase line pressure.

d. Bad gas valve.

d. Replace gas valve.

Содержание Miraclean 2000

Страница 1: ...tions 1 Damage in Shipment 1 Positioning 1 Ventilation 1 National Code Requirements 1 Gas Connections and Pipe Size 2 Flexible Gas Connections Quick Disconnect Devices 2 Leveling 2 Lighting Instructio...

Страница 2: ...GAS MAY EVENTUALLY LOSE ITS ODOR AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE THAT PROPANE GAS IS NOT PRESENT EVEN THOUGH YOU DO NOT DETECT AN ODOR IF THERE IS ANY DOUBT YOU SHOULD CALL YOUR LOCAL PROPAN...

Страница 3: ...y the carrier DO NOT RETURN DAMAGED MERCHANDISE TO KEATING FILE YOUR CLAIM AS ABOVE FIRST STEPS POSITIONING Keep appliance area free and clear of any combustibles Position the Miraclean Griddle 6 inch...

Страница 4: ...cal gas company to assure adequate volume and pressure Refer to serial plate for proper gas requirement for your particular model FLEXIBLE GAS CONNECTORS AND QUICK DISCONNECT DEVICES For an appliance...

Страница 5: ...heat of the Miraclean has an emissivity of 078 You can prove this to yourself by holding your hand approximately 1 2 above the Miraclean Griddle plate At this distance it is difficult to tell whether...

Страница 6: ...quality food products Follow cooking procedures below COOKING INSTRUCTIONS 1 Set the thermostat to the desired temperature and wait ten minutes for preheat The operating temperature should be from 10...

Страница 7: ...ith Keating Klenzer Polish with a soft cloth towel It will sparkle like new in just a few minutes Rinse with potable water to remove excess Keating Klenzer Proper care should be taken to fully clean t...

Страница 8: ...urate thermometer on surface over thermostat bulb Use the inverted V on the front of the griddle plate to locate thermostat bulb Place the surface thermometer about half way toward the back of the pla...

Страница 9: ...TEM DESCRIPTION PART NUMBER 1 SPARK IGNITION ASSEMBLY SEE Item 4 Figure 6 2 2 THERMOPILE 022770 3 PILOT TUBE 1 4 007998 4 PILOT ASSEMBLY 029769 ALL NATURAL GAS 24 30 029599 LP 24 39 BEF NATURAL GAS OR...

Страница 10: ...the screws 2 Disconnect the wires on the switch and remove switch 3 Snap the new switch into place and reconnect all wires 4 Return the control panel to its normal position THERMOSTAT REMOVAL AND REPL...

Страница 11: ...having a 1 1000MV range Conduct each check below by connecting meter test leads to terminals as indicated All readings are closed circuit A BURNER COIL CHECK A Reading Thermostat contacts CLOSED Gas V...

Страница 12: ...een 75 millivolts and 25 millivolts If dropout occurs outside these limits change the valve WARNING AND OPERATING PLATES All warning and operating plates on the Keating MIRACLEAN Griddle should be in...

Страница 13: ...e to 4 e Gas valve failure e Replace valve Temperature of a Thermostat is not calibrated a Calibrate thermostat with exhaust griddle erratic system running b Air from exhaust hood excessive b Have exh...

Страница 14: ...TY AGAINST LATENT DEFECTS E XCLUSIONS The warranties provided by Keating of Chicago Inc do not apply in the following instances 1 Defects arising out of or resulting from improper installation or main...

Страница 15: ...________________________ ADDRESS ______________________________________________________________________________________________________ CITY ___________________________________________________________...

Отзывы: