System operation
System operation
P+
A
B
cosphi
0,95
0,95
cosphi1 = 1,0
untererregt
under-exited
(induktiv
inductiv
übererregt
over-
exited
(kapazitiv
capactiv)
P+
100 kW
69 kW
129 kW
46%
Punkt 1
point 1
cosphi 0.950 kap.
66%
Punkt 2
point 2
cosphi 1,0
86%
Punkt 3
point 3
cosphi 0,950 ind.
Hyst.
12kW
Hyst.
12kW
46 %
66 %
86 %
Hyst.
12kW
Hysteraese = 12 kW (+/- 6 kW
hysteresis = 12 kW (+/- 6 kW)
NOTE
In the event of negative active power, the curve behaves in the same way.
Example 2: Settings:
Mode
P
3
φ
Cosphi1 1.0
Power consumption
P rated=Pmax.
150kW (=100%)/for power recovery systems -150kW
t-delay
000 seconds
Hysteresis 0%
Point 1
P= 0.0%
cosφ = 1.0.
Point 2
P= 50% (= 75 kW)
cosφ = 1.0.
Point 3
P= 55% (= 82.5 kW)
cosφ = 0.984 ind.
Point 4
P= 85% (= 127.5 kW)
cosφ = 0.900 ind.
Point 5
P= 100% (= 150 kW)
cosφ = 0.900 ind.