Commissioning
3.2
Default settings after reset
Primary voltage/secondary voltage
400 V/400 V Ph-Ph
Primary current/secondary current
1000 A/5 A
Cosφ 1 (target cosφ)
inductive 0.95
Cosφ 2 (target cosφ with energy recovery) inductive 1.00
Cosφ 3 (alarm cosφ for FTS message)
inductive 0.92
Damping coefficient for current and
voltage
2
Temperature measurement
Active
Switching threshold fan
28°C, hysteresis 5°C
Operating point alarm
45°C, hysteresis 5°C
Operating point emergency off
48°C, hysteresis 5°C
Idle time
30 sec.
Alarm relay time
1200 sec.
Alarm relay
NC contact
Hysteresis connection
70% of smallest available stage
Hysteresis switch-off
100% of smallest available stage
Switch attenuation (stage interval)
8 sec.
Operating cycle limit
80,000
Stage power
No stage power programmed
Stages
System type standard
Discharge time 180 sec.
Detuning 7 %
Cabinet No. 1
Stage 5 as fan