V7.00
24905_EDEBD
A0272-5019-1_EN
56
System operation
5.13.6 Q-Control:
The following modes can be selected:
DI
3
Q/P rated (change by digital input)
AI
3
Q/P rated (change by analog input)
U
3
Q/P rated (change by voltage curve)
P
3
Q/P rated (change by active power curve)
off
The function is deactivated, i.e. the device is working with the
value programmed as target cosine1
Parameters:
Q parameters
Q-Control Yes/No
P rated
100.0 kW
Target Q
Q/Pn1 power consumption
0.75 capacitive to 0.75 inductive
Q/Pn2 energy recovery
0.75 capacitive to 0.75 inductive
Q/Pn3 Alarm
0.00 to 1.73 inductive
Mode DI
3
Q
t-delay
000 Seconds
Q/Pn A
0.50 ind.
Q/Pn B
0.33 ind.
Q/Pn C
0.33 cap.
Q/Pn D
0.50 cap.
Mode AI
3
Q
t-delay
000 Seconds
Q/Pn A
0.90 ind.
Q/Pn B
1
% A
0%
% B
100%
AI 4–20 mA
YES