Operating instructions
multicomp
Version 1.00
Page 29 of 29
ED
EBD
A
014
4
/ 05
11
-1
GB
12
Selection of lines and fuses
C power
(400 V)
Q (kvar)
Current input
per phase
I (A)
Supply line
Cu (mm²)
Fuse protection
slow-blowing
3 x I (A)
0.5
1
1.5
2
2.5
3
4
5
6
7.5
10
12.5
15
16.7
20
25
30
33.3
35
40
45
50
60
70
75
80
90
100
120
125
150
180
200
250
300
350
400
450
500
0.72
1.44
2.16
2.88
3.60
4.32
5.76
7.20
8.64
10.80
14.40
18.00
21.60
24.00
28.80
36.00
43.20
48.00
50.40
57.60
64.80
72.00
86.40
100.80
108.00
115.10
129.60
144.00
172.80
180.00
216.00
259.20
288.00
360.00
432.00
504.00
576.00
648.00
720.00
4 x 1.5
4 x 1.5
4 x 1.5
4 x 1.5
4 x 1.5
4 x 1.5
4 x 1.5
4 x 2.5
4 x 2.5
4 x 2.5
4 x 2.5
4 x 6
4 x 10
4 x 10
4 x 10
4 x 16
4 x 16
4 x 16
4 x 25
4 x 25
3 x 35/ 16
3 x 50/ 25
3 x 50/ 25
3 x 70/ 35
3 x 70/ 35
3 x 95/ 50
3 x 95/ 50
3 x 95/ 50
3 x 120/ 70
3 x 120/ 70
3 x 150/ 70
3 x 240/120
3 x 240/120
2 x
3 x 150/ 70
2 x
3 x 185/ 95
2 x
3 x 240/120
2 x
3 x 240/120
4 x
3 x 120/ 70
4 x
3 x 150/ 70
10
10
10
10
10
10
10
16
16
16
25
35
35
35
50
63
80
80
80
100
100
125
125
160
160
200
200
250
250
250
315
400
400
500
630
2 x 400
2 x 400
2 x 500
2 x 500