11.4 Device memory
11.5 Other limits
11.6 Power supply
11.7 Hardware inputs and outputs
11.7.1 Hardware inputs
Measuring input for
voltage
U
PH-N
or
U
PH-PH
30V ... 690V ... 790V AC
Direct impedance
750 kOhm
Measuring range
1 measuring range, measurement voltage transformer programmable
Measuring input for
current
I
L1
or I
L2
or I
L3
0.015A ... 5A ... 6A AC
Power consumption
≤
2VA at 6A
Measuring range
1 measuring range, current transformer programmable
11.7.2 Hardware outputs
Alarm relay
Switching capacity
250 V (AC) / 2 A potential-free
Capacitor
stage relay
Switching capacity
250 V (AC) / 2 A potential-free
11.8 Electrical connection
Data storage
16 kB RAM volatile
Program and parameter memory
128 kB flash
Extreme values (Max.)
Missing compensation power Q
max
Limit violations:
acquisition time
harmonics
approx. 100 ms
Overvoltage disconnect:
acquisition time
approx. 40 ms
No voltage disconnect:
acquisition time
approx. 40 ms (for measurement voltage)
Power supply
85 to 265V AC/DC; max. 12 VA, 6 W
Connection elements
Plug-in terminals
Permissible cross section of the connection lines
2.5 mm
2
Measurementmeasur
ement current voltage
inputs
Fuse protection
max. 6 A
measurement current
input
Fuse protection
NONE!!! Always short-circuit current transformer terminals k and l
prior to opening the circuit!
Input
Control voltage
Fuse protection
max. 6 A
Relay output
Fuse protection
max 2 A medium time-lag
Transformer
connection
Connections
See connection chart