Operating instructions
multicomp
Version 1.00
Page 17 of 29
ED
EBD
A
014
4
/ 05
11
-1
GB
7.4
Stage state window
Selection of submenus with button
W
.
In the submenus of this window, it is displayed whether or not the capacitor stages connected are working in
automatic operation, or if they are switched on or off permanently. The individual capacitor stages can be
selected by pressing button
W
.
By pressing the buttons
U
to start entering values,
V
to change and
X
to save them, you can change the
stage state from
Auto
(Automatic) to
Off
(switched off permanently) or
On
(switched on permanently).
7.5
Service window:
Selection of submenus with button
W
.
In the submenus of this window, the number of connections of each individual capacitor stage is displayed. In
the Delete switching cycles menu item, the cumulated switching cycles can be deleted for all stages. This is
done by simultaneously pressing the buttons
U
and
V
.
If the number of switches equals or exceeds the value set in the menu item Extras / Switching cycle limit, a
message is displayed, depending on the settings in the Error message menu / Switching cycle limit
exceeded.
In addition, the value in the menu item Missing Comp. power maximum can be deleted by simultaneously
pressing the buttons
U
and
V
, resetting the message Facility too small. In case the set target CosPhi is
not reached despite all available stages switched on, this message is displayed after the set alarm delay time
has elapsed. The alarm delay can be set in the menu Switching performance / Alarm delay.
S t a g e s t a t e
n e x t
î
D
b
Note!
Capacitor stages permanently switched on or off are not available to
calculate the optimizing automatic operation.
S e r v i c e
n e x t
î
D