KBR multicomp F144-3PH
V2.00
16
19837_EDEBD
A0227-1816-1_EN
Connecting the multicomp
Basic system parameters switching performance:
Hysteresis connection:
100% of smallest stage power
Hysteresis disconnection:
100% of smallest stage power
Alarm delay:
1200 seconds (20 minutes)
Idle time:
10 seconds
Switching interval:
8 seconds
Attenuation coefficient for current:
2
Attenuation coefficient for voltage:
2
Attenuation coefficient Qmiss:
2
Basic system temperature parameters:
Measurement:
active
Switching thresholds:
Fan switched on:
28°C
Fan switched off:
23°C
Stages switched on:
43°C
Stages switched off:
48°C
Basic system limit parameters:
Operating cycle limit:
80000 connections
Operating cycle count:
Activated by set limit
Overvoltage limit:
440 VAC PhPh (corresponds to 10 %)
Current low load limit:
0.01 A
Average current limit:
1200 A
THD limit:
8% (0% = monitoring deactivated)
activated by set limit
Limit Id:
0 % (0% = monitoring deactivated)
activated by set limit