V2.00
KBR multicomp F144-3PH
29
19837_EDEBD
A0227-1816-1_EN
Display as example:
Main menu:
= cosφ actual (instantaneous)
Stage mode:
= all stages automatic on
Menu description:
= cosφ actual (instantaneous)
Measured cosφ:
= 0.64 inductive
Missing compensation power:
= 22.4 kvar
By pressing the button
N
twice, you can display the
maximum value of
the missing compensation power
. The value is displayed in kvar. The value is
only displayed if all available stages are switched on and the configured alarm
CosPhi is not reached when the set alarm delay time has elapsed.
As soon as the value has been entered, the status
Facility too small
is displayed
in the Messages sub menu.
In case of a 3-phase measurement, the values in the measurement display areas
are displayed separately per individual phase. In case of single-phase measure-
ment, only the value of the phase measured is displayed
Note
Main menu cos φ