KBR multicomp F144-3PH
V2.00
22
19837_EDEBD
A0227-1816-1_EN
Start-up guideline
After re-connecting it to the voltage supply, the controller has to start auto-
matically. If the cosφ voltage is read in the cosφ act. menu immediately after
switching it on, the value for cosφ should be low and inductive. After approx. 60
seconds, the controller starts to switch on the individual capacitor stages.
The cosφ, which can be read in the cosφ act. menu, should have risen in
comparison with former values, or it should rise when switching on additional
stages. If the compensation unit is dimensioned correctly, the controller should
compensate the set target cosine after a certain period of time.
4.4
Basic device programming:
The menu guidance of the multicomp is self-explanatory. The operator is
guided and supported by the device through operating instructions displayed
for the respective situation. The following terms are available for programming:
Enter
Return for configuration
EDIT Perform configuration
¯
Submenu or parameter selection
+
Value input
Selection
YES Confirmation to save configuration
NO
Discard configuration
¡
Return
As an example of the basic configuration procedure, the functions in the
Extra /
Commissioning
menu will be looked at more closely.
Menu item: Transformer
Transformer
Menu description
Pp
O
N
M
ENTER
Display hot-key area
|
|
|
|
|
|
|
Return for configuration
|
|
Menu selection
|
Menu selection
Return