KBR multimess D9-PQ
20144 EDEBD
A0228-5023-1_EN
14
Voltage inputs
Channels
U
1
, U
2
, U
3
, U
N/E/4
Electrical safety
DIN EN 61010
300V CAT IV
600V CAT III
Input reference level
PE
Impedance -> PE
10 MΩ || 25pF
Nominal input voltage Un 100V AC /230VAC
Full scale range (FSR)
0…480VAC L-E
Waveform
Jede
Maximum crest factor
@ Un
3
Nominal power
frequency fn
50 Hz / 60 Hz
Bandwidth
DC…20kHz
Frequency range of the
fundamental
fn ± 15%
42,5..50..57,5Hz
51,0..60..69,0Hz
Accuracy
Fundamental, r.m.s
±0,1% Un
(0°C…45°C)
±0,2% Un (-25°C…
55°C) @ 10%...150%Un
Fundamental, Phase
±0.01°
@ 10%...150%Un
Harmonic n = 2..50,
r.m.s.
±5% of reading
@ Uh ≥ 1% Un
±0.05% Un
@ Uh < 1% Un
Harmonic n = 2..50,
Phase
±n∙0.01°
@ Uh ≥ 1% Un
Interharmonic n = 1..49,
r.m.s.
±5% of reading
@ Uih = ≥ 1% Un
±0.05% Un
@ Uih < 1% Un
Power frequency
±10mHz
@ 10%...200%Un
Flicker
DIN EN 61000-415:2011
Class F2
Dip residual voltage
±0.2% Un
@ 10%..100%Un
Dip duration
±20ms
@ 10%..100%Un
Swell residual voltage ±0.2% Un
@ 100%..150%Un
Swell duration
±20ms
@ 100%..150%Un
Interruption duration
±20ms
Voltage inputs
@ 1%..100%Un
Voltage unbalance
±0.15%
@ 1%..5% reading
Mains signaling
voltage (< 3kHz)
±5% of reading
@ Us = 3%..15% Un
±0.15% Un
@ Us = 1%..3% Un
Current inputs
Option
C30
C31
Channels
I1, I2, I3, IN/4
Electrical safety
DIN EN 61010
300V CAT III
Input type
Differential, isolated
Impedance
≤ 4mΩ
Nominal input current In 1 A AC / 5 A AC
Full scale range (FSR)
10A
AC
100A
AC
Overload capacity
permanent
≤ 1s
≤ 10ms
≤ 5ms
10 A
30 A
100 A
500 A
Waveform
AC, any
Maximum crest factor
@ In
4
Bandwidth
25Hz...20kHz
Accuracy
Fundamental, r.m.s
< 0,1% FSR
5%...100%
< 0,2% FSR
5% ... 10%
Fundamental, Phase
±0,1°
5%...100%
±0,2°
5% ... 10%
Harmonic n = 2..50,
r.m.s.
5%
5%...100%
10%
5% ... 10%
Harmonic n = 2..50,
Phase
±n∙0,1°
5%...100%
±n∙0,2°
5% ... 10%
Interharmonic
n = 1..49, r.m.s.
±5%
5%...100%
±10%
5% ... 10%