Kaysun KTHR-190 Скачать руководство пользователя страница 25

23

Error  phenomenon

Possible reason & Solution

Displayed temperature after sterilization

Deviation from set temperature

● Sterilization is completed after a period of time, the current display temperature and the user set

temperature is not consistent with the normal phenomenon. It takes a long time for the water tank

temperature to decrease from 70

ć

 to the user setting temperature;

● Turn on the forced sterilization or automatic sterilization, the set temperature of the unit becomes 70

ć

 (once

effective). The sterilization symbol of the heating process lights up. After the water tank temperature

reaches 70

ć

 to complete the sterilization, the sterilization icon goes out.

Deviation of display from set temperature.

When the unit reaches the temperature and stops, there may be a small deviation between the display

temperature and the set temperature, which is a normal phenomenon.

The unit heats up for a period of time and

shows that the temperature has not risen.

● If the user continues to use hot water, resulting in the lower part of the tank into the more cold water, the

unit mainly heats the lower part of the water temperature, the priority of the temperature under the tank

rises while the upper part of the tank does not rise significantly is a normal phenomenon.

● Check whether the host is working properly and the tank setting operation mode, the tank energy-saving

mode host heating hot water to the maximum water temperature will stop working, using electric heating

heating, check whether the electric heating is working properly.

Malfunction Description

Display

Machine working parameters are abnormal.

EH00

Tank and LCD panel communication error.

Eh0b

Faulty communication between water tank and 

outdoor unit

EL01

Leakage protection

PH15

Error of TP

Error of T3

Error of T5U

EC54

Error of T4

EC53

EC52

6.5  Error code shooting table

EH5L

EH5U

EH5d

Error of T5L

Electric heating disconnection protection

Malfunction Description

Display

Abnormal operating parameters of the outdoor unit

EC51

Dry burning protection

PHdH

Anti-freeze protection for refrigeration status

PH23

Anti-freeze protection for low-temperature conditions

PH24

DC fan out of phase

EC72

PC01

Main control voltage protection

PC40

Outdoor main control & driver chip communication failure

PC43

Compressor phase failure protection

PC44

Compressor 0 speed protection

PC45

341PWM Synchronization Guarantee

PC12

341 Voltage protection or MCE fault

Compressor overcurrent protection

PC49

Compressor stall protection

PC46

Compressor feedback protection

PC04

T2 high temperature protection

PC51

T2 low temperature protection

PC52

PC08

Outdoor unit current protection

Over-temperature protection for water tanks

PH9b

EC07

Outdoor unit fan stall protection

PC00

IPM module protection

PC03

System pressure protection or failure

PC02

Compressor top temperature protection

Содержание KTHR-190

Страница 1: ...roduct Before using your unit please read this manual carefully and keep it for future reference If you need to consult the electronic manual please go to this website https www kaysun es INSTALLATION...

Страница 2: ......

Страница 3: ...ent device RCD with the rating not exceeding 30mA shall be incorporated in the fixed wiring according to the national rule The handle of PTR valve should be pulled out once per half a year to make sur...

Страница 4: ...pressure relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked NOTE All the picture in this manual are for explanation purpose only They may be slight...

Страница 5: ...E Above calculation is based on the ideal condition the final cost bill will be different caused by the actual running conditions such as running period ambient temperature etc 1 SAFETY INFORMATION Pl...

Страница 6: ...hildren For appliances which contain button or non lithium batteries The battery can cause serious injuries if it is swallowed or placed inside any part of the body If you think batteries might have s...

Страница 7: ...off or pull out the power plug Otherwise an electric shock and injury may be caused Water temperature over 50 can cause severe burns instantly from scalds Children disabled and elderly are at highest...

Страница 8: ...to the outdoor unit s instruction manual The unit should be located in an area not subject to freezing temperatures The unit located in unconditioned spaces i e garag es basements etc may require the...

Страница 9: ...ease ensure the vertical and reliable installation of the tank and the necessary space for installation and maintenance Fixing method WARNING The appearance of the water tank and the orientation of th...

Страница 10: ...installed in inclosed space The water heater must be located in a space 15m and must have unrestricted air flow As an example a room that has an 2 5 tall ceiling and is 3 meters long by 2 meters wide...

Страница 11: ...he One Way Valve thread in accessories is RC3 4 It is used to prevent water from flowing backwards After water system piping work turn on the cold water inlet valve and hot water outlet valve and star...

Страница 12: ...arge amount 1 84kg there are no additional minimum floor area requirements In case of total refrigerant amount 1 84 kg the unit should be installed operated and stored in a room with a floor area larg...

Страница 13: ...Cord mm2 Manual Switch A Capcity Fuse A Model Name Power Supply Min Diameter of Power Supply Cord mm2 220 240V 50Hz KTHR 190 1 5 For water tank with electric heating 1 5 For water tank with electric...

Страница 14: ...e properly installed with a discharge pipe run to an adequate drain and sheltered from freezing All piping properly installed and free of leaks Unit completely filled with water Water temperature limi...

Страница 15: ...ficient inlet water pressure between0 15MPa and 0 65MPa 4 2 1 Checking list before commisionning Emptying Drainpipe shut off valve Close After emptying please replace the nut of drainpipe Close Open D...

Страница 16: ...the switch is closed the unit will be stopped forcibly If switch breaks the unit can run normally according settings No Hour low bit Min high bit Min Low bit unit Explenation 12 13 14 8 9 10 11 7 TP...

Страница 17: ...lock Whenever there is any setting for clock There are daily or weekly TIMER icon If anyone of them has been set this icon will lighten the corresponding one when screen is unlocked If there is none o...

Страница 18: ...as been running for a long time without reaching the set Temp 10 11 12 Error It will be lightened when unit is under protection error VACATION MODE For the outgoing vacation mode the water tank is set...

Страница 19: ...s the TIMER button to the day timer icon press the confirmation button to enter the day timer setting interface the day timer has a total of 6 time periods each time period can be set to open the time...

Страница 20: ...tion of the up down button or pressing the return button or the power on off button you can directly exit the date and time setting 3 Setting can be done in both power on and power off state Child loc...

Страница 21: ...es 3 The 2 4GHz preferable or 5GHz band wireless signal is enabled on your wireless router Android Phone users scan Android QR code or go to google play search Nethome Plus App and download it IOS use...

Страница 22: ...US SK106 EU SK106 FCC ID 2ADQOMDNA22 IC 12575A MDNA22 US SK109 EU SK109 EU SK110 US SK110 FCC ID 2ADQOMDNA23 IC 12575A MDNA23 In Canada CAN ICES 3 B NMB 3 B Le pr sent appareil est conforme aux CNR I...

Страница 23: ...eration on panel for 1 min unit will lock the panel shows to unlock the panel please press the button for 2 seconds Q Why sometimes there is some water flowed from drainage pipe of PTR valve A Because...

Страница 24: ...nnot be started within 3 minutes of stopping The water heater cannot run for about 3 minutes after running stops when the power switch is turned on The water temperature is displayed as dropping Low a...

Страница 25: ...nk setting operation mode the tank energy saving mode host heating hot water to the maximum water temperature will stop working using electric heating heating check whether the electric heating is wor...

Страница 26: ...flow out Get off the anode rod Replace with a new one and make sure effective sealed Open cold water inlet tap untill water flows out from outlet tap then turn of water outlet tap Power on then resta...

Страница 27: ...in water tank and the pipeline and close all the valves Check the inner components regularly 7 2 Recommended regular maintenance table 7 1 Maintenance 8 Turn off the power and turn off the water inlet...

Страница 28: ......

Отзывы: