52
6
Alarm signal and Sterilization module
Refer to the following figure for the wiring of alarm signal and Sterilization module.
CAUTION
The output voltage is 220-240V~.
NOTE
The Sterilization function needs to be active by the wired controller, refer to the manual of wired controller
for the detail setting.
Other optional in-series equipment may be connected, contact the agent for detail.
7
Remote On/Off control
Refer to the following figure for using Remote On/Off control.
Remote Switch
Air Conditioning System
On
Off
Off
On
NOTE
The priority of remote control is higher than that of the wired controller.
More remote control functions, such as delayed control, air conditioning system is on when remote
control is on, please refer to the manual of wired controller.
8
Reclose the electric control box cover
Straighten out the connecting wires and lay them flat, and separate and fix the strong- and weak-current
cables with cable clamps.
CAUTION
Do not cover the electric control box during power-on.
When covering the electric control box, arrange the cables carefully and do not clip the connecting
wires on the electric control box cover.
Main
control
board
Alarm signal output
Output voltage: 220 VAC;
Maximum output power: 220 W
CN22
Strong current
sterilization module
N
Output voltage: 220 VAC;
Maximum output power: 220 W
Remote switch signal
IN GND
CN55
Main control board