11
● The minimum interval of data packet is 100 ms. In case of
excessive data in a single data packet, adjust the time interval
appropriately.
Command
Register
Address
Parameter Name
Parameter Range
Default
Value
03/06/16
12
Whether anti-freezing
protection is enabled 00: OFF; 01: ON
0
03/06/16
13
Anti-freezing setting
temperature
0° ~20°C / 32°F~68°F
5°C / 41°F
03/06/16
14
Centralized control
locking
00: OFF; 01: ON
0
03/06/16
15
System type
00: Two-pipe cooling and
heating
01: Two-pipe cooling
02: Two-pipe cElectric
auxiliary heating
03: Two-pipe hElectric
auxiliary heating
04: Two-pipe cooling and
hElectric auxiliary
heating
05: Four-pipe
0
03
16
Restore factory
settings
0: General; 1: Restore factory
settings
0
03
17
High fan speed status 00: OFF; 01: ON
0
03
18
Medium fan speed
status
00: OFF; 01: ON
0
03
19
Low fan speed status 00: OFF; 01: ON
0
03
20
Valve 1 status
00: OFF; 01: ON
0
03
21
Valve 2 status
00: OFF; 01: ON
0