09
Parameter
Code
Parameter Name
Parameter Range
Default
Value
Remarks
C0
Wired controller address 01-32
01
C1
Two-pipe/four-pipe
selection
00: Two-pipe cooling and heating
01: Two-pipe cooling
02: Two-pipe cAuxiliary
electric heater
03: Two-pipe hAuxiliary
electric heater
04: Two-pipe cooling and heating
+Auxiliary electric heater
05: Four-pipe
00
C2
ECO cooling
temperature setting
17°C to 30°C / 62°F to 86°F
26°C / 86°F
Stepping
0.5°C /1°F
C3
ECO heating
temperature setting
17°C to 30°C / 62°F to 86°F
18°C / 64°F
Stepping
0.5°C /1°F
C4
Anti-freezing protection 00: Off 01:Start
00
C5
Anti-freeze temperature
setting
0°C to 20°C / 32°F to 68°F
5°C / 41°F
Stepping
0.5°C /1°F
C6
Baud rate setting
00: 4800 01: 9600
01
C7
Celsius/Fahrenheit
00: °C 01: °F
00
C8
Button backlight
setting
00: Off 01: On
01
C9
Language
00: Chinese 01: English
01
C10
Temperature
compensation
-3°C to 3°C (Min. 0.5°C)
-6°F to 6°F (Max. 1°F)
0
C11
Temperature return
difference
1, 2, 3 (°C) / 2, 4, 6 (°F)
1° C / 2°F
C12
Fan always on/always
off (After setting
temperature)
00: Always on 01: Always off
0
C13
Version
Read only
Note: The “ ” indicates the function is not supported if non-networked.