PRODIGY Technical Manual
57
I
PM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
N
U
V
V
W
W
(+)Red
9.2.8 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check the power supply
Check the connections and
wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Power on and when the unit is in standby,
check if the voltage between P and N is
around DC 310V or 340V or 380V? Then
start up the unit, measure the voltage
between P and N. Is it in 220V~400V?
Check the reactor
Yes
No
Replace outdoor main PCB
Содержание KAE-26 DN7
Страница 1: ...PRODIGY 3D Inverter Technical Manual ...
Страница 11: ...PRODIGY Technical Manual 11 For KAY 26 DN7 ...
Страница 12: ...PRODIGY Technical Manual 12 For KAY 35 DN7 For KAY 52 DN7 ...
Страница 13: ...PRODIGY Technical Manual 13 For KAY 71 DN7 ...
Страница 14: ...PRODIGY Technical Manual 14 3 2 Outdoor Unit ...
Страница 15: ...PRODIGY Technical Manual 15 For KAE 26 DN7 ...
Страница 16: ...PRODIGY Technical Manual 16 For KAE 35 DN7 KAE 52 DN7 ...
Страница 17: ...PRODIGY Technical Manual 17 For KAE 71 DN7 ...
Страница 64: ......