PRODIGY Technical Manual
40
8.4.5 Drying mode
Indoor fan speed is fixed at breeze and can‟t be changed. The louver angle is the same as in cooling
mode.
All protections are active and the same as that in cooling mode.
8.4.6 Forced operation function
Forced cooling mode:
The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for
30 minutes, AC will turn to auto mode with 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24
℃
setting temperature.
When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting, fan speed
setting, sleeping mode setting, follow me setting, it will quit the forced operation.
8.4.7 Economy function
8.4.7.1 The sleep function is available in cooling, heating or auto mode.
8.4.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours
later the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function
has the priority).
8.4.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.
8.4.7.4 Timer setting is available
8.4.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart
module. In case of a sudden power failure, the module memorizes the setting conditions before the
power failure. The unit will resume the previous operation setting (not including swing function)
automatically after 3 minutes when power returns.
If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes
and turn to auto mode as 24
℃
setting temp.
If AC is off before power off and AC is required to start up now, the compressor will have 1 minute
delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
8.4.9 Refrigerant Leakage Detection
With this new technology, the display area will show
“EC” when the outdoor unit detects refrigerant
leakage.
8.4.10 8
℃
Heating(optional)
In heating operation, the preset temperature of the air conditioner can be as lower as 8
℃
, which keeps
the room temperature steady at 8
℃
and prevents household things freezing when the house is
unoccupied for a long time in severe cold weather.
Содержание KAE-26 DN7
Страница 1: ...PRODIGY 3D Inverter Technical Manual ...
Страница 11: ...PRODIGY Technical Manual 11 For KAY 26 DN7 ...
Страница 12: ...PRODIGY Technical Manual 12 For KAY 35 DN7 For KAY 52 DN7 ...
Страница 13: ...PRODIGY Technical Manual 13 For KAY 71 DN7 ...
Страница 14: ...PRODIGY Technical Manual 14 3 2 Outdoor Unit ...
Страница 15: ...PRODIGY Technical Manual 15 For KAE 26 DN7 ...
Страница 16: ...PRODIGY Technical Manual 16 For KAE 35 DN7 KAE 52 DN7 ...
Страница 17: ...PRODIGY Technical Manual 17 For KAE 71 DN7 ...
Страница 64: ......