PRODIGY Technical Manual
36
8.4 Operation Modes and Functions
8.4.1 Fan mode
(
1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
a
b
c
d
T1
e
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
When T1- Ts <
ΔT -2
℃
, the compressor will stop,
when T1
—
Ts >
ΔT -0.5
℃,
the compressor will be activated.
ΔT is the programmed parameter of temperature compensation.
When the AC run in mute mode, the compressor will run with low frequency.
When the current is more than setting value, the current protection function will be activated, and the
compressor will stop.
8.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different.
T4
A+
A
B
C
D
E
8.4.2.3Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
When the setting temp. is reached, if the compressor stop running, indoor fan motor will run in
Minimum speed or setting speed.
The indoor fan is controlled as below:
Содержание KAE-26 DN7
Страница 1: ...PRODIGY 3D Inverter Technical Manual ...
Страница 11: ...PRODIGY Technical Manual 11 For KAY 26 DN7 ...
Страница 12: ...PRODIGY Technical Manual 12 For KAY 35 DN7 For KAY 52 DN7 ...
Страница 13: ...PRODIGY Technical Manual 13 For KAY 71 DN7 ...
Страница 14: ...PRODIGY Technical Manual 14 3 2 Outdoor Unit ...
Страница 15: ...PRODIGY Technical Manual 15 For KAE 26 DN7 ...
Страница 16: ...PRODIGY Technical Manual 16 For KAE 35 DN7 KAE 52 DN7 ...
Страница 17: ...PRODIGY Technical Manual 17 For KAE 71 DN7 ...
Страница 64: ......